CV500TDL21 Omron, CV500TDL21 Datasheet - Page 5

no-image

CV500TDL21

Manufacturer Part Number
CV500TDL21
Description
Programmable Logic Controller
Manufacturer
Omron
Datasheet

Specifications of CV500TDL21

Peak Reflow Compatible (260 C)
No
Leaded Process Compatible
No
Lead Free Status / RoHS Status
Contains lead / RoHS non-compliant
E5ZE-8j-E
J DISPLAY UNIT
Ratings
Characteristics
J COMMUNICATIONS
Functions Set via Communications
Supply voltage
Operating voltage range
Power consumption
Setting method
Display method
Other functions
Sampling period
Enclosure ratings
Vibration resistance
Shock resistance
Ambient temperature
Ambient humidity
Weight
Communications type
Maximum total cable length
Communications method
Connection method
Transmission line configuration
Transmission line type
Synchronization method
Baud rate
Transmission code
Number of stop bits
Parity
Character length
Error detection
Communications unit number
Transmission and reception switching time
Temperature controllers connected to
single host computer
S Set point
S Process value
S Alarm value
S Alarm mode
S Hysteresis
S Proportional band
S Integral time
100 to 240 VAC, 50/60 Hz or 24 VDC
85% to 110% of rated supply voltage
Approx. 8 VA at 100 VAC to 12 VA at 420 VAC; approx. 5 W at 24 VDC
Digital setting via Up and Down keys
LED character heights: PV: 15 mm (red); SV: 11 mm (green); UNIT/CH/BK: 11 mm (orange)
Key protection
Display group selection
Display scan function
500 ms, 1 s (selectable)
Front panel: IP50
Rear case: IP20
Terminals: IP00
Malfunction: 2 to 55 Hz, 19.6 m/s
Malfunction: 196 m/s
–10 °C to 55°C (4°F to 131°F) with no icing
35% to 85% RH
Approx. 450 g
RS-232C
15 m
Half-duplex
25-pin D-sub connector
3-wire
Direct line
Start-stop synchronization (asynchronous)
2,400/4,800/9,600/19,200 bps
ASCII
2
Even parity
7 bits
Vertical parity and FCS (frame check sequence)
0 to F (hexademical)
–––
–––
S Derivative timer
S Output value
S Auto-turning (AT) start–stop
S Heater burnout detection set value
S Control start/stop
S Control memory bank
S Cooling start/stop
2
for 3 times in each of 6 directions
2
for 10 min each in X, y, and Z directions
RS-422
500 m
5-pole terminal block with M3 screws
4-wire
Multi-drop line
20 ms max.
16 max.
S Control memory bank
S Cooling coefficient*
S Deadband/overlap band*
S Fuzzy strength
S Fuzzy scale 1, 2
*Heating and cooling control models only
RS-485
500 m
2-wire
E5ZE-8j-E
217

Related parts for CV500TDL21