E5C2-R20P 110'C 230VAC Omron, E5C2-R20P 110'C 230VAC Datasheet - Page 2

TEMPERATURE CONTROLLER, 100C

E5C2-R20P 110'C 230VAC

Manufacturer Part Number
E5C2-R20P 110'C 230VAC
Description
TEMPERATURE CONTROLLER, 100C
Manufacturer
Omron
Datasheet

Specifications of E5C2-R20P 110'C 230VAC

Thermocouple Type
PT100
Operating Temperature Max
100°C
Operating Temperature Min
0°C
Output Voltage Max
250VAC
Svhc
No SVHC (15-Dec-2010)
Accuracy
± 2%
Accuracy %
2%
Approval Bodies
CE, CSA, UL
Specifications
■ Ratings
Note: Specify either 100/110/120 VAC or 200/220/240 VAC when ordering.
■ Input Ranges
Note: 1. Values in ( ) are the minimum unit.
■ Characteristics
Note: 1. No reset function is incorporated by any E5C2 model with ON/OFF control.
2
Supply voltage
Operating voltage range
Power consumption
Input
Control mode
Setting method
Indication method
Control output
Range
Setting accuracy
Hysteresis
Proportional band
Control period
Reset range (see note 1)
Insulation resistance
Dielectric strength
Vibration resistance
Shock resistance
Life expectancy
Ambient temperature
Ambient humidity
Degree of protection
Weight
2. Values in ( ) are the thermistor resistive value.
2. The model number of the special watertight cover conforming to IP66, NEMA4 is Y92A-48B.
Input
Temperature Controller
°C
°F
0 to 200 (5),
0 to 300 (10),
0 to 400 (10),
0 to 600 (20),
0 to 800 (20),
0 to 1,000 (25),
0 to 1,200 (25)
32 to 392 (10),
32 to 572 (20),
32 to 752 (20),
32 to 1,112 (40),
32 to 1,472 (50),
32 to 1,832 (50),
32 to 2,192 (50)
Chromel vs. alumel
K (CA)
±2% FS max.
Approx. 0.5% FS (fixed)
3% FS (fixed)
Approx. 20 s
5 ±1% FS min.
20 MΩ min. (at 500 VDC)
2,000 VAC, 50/60 Hz for 1 min between charged terminals and uncharged metallic parts
Malfunction: 10 to 55 Hz, 0.15-mm single amplitude for 10 min each in X, Y, and Z directions
Destruction: 16.7 Hz, 2-mm double amplitude for 2 hrs each in X, Y, and Z directions
Malfunction: 147 m/s
Destruction: 294 m/s
Electrical:
Operating: –10°C to 55°C (with no icing or condensation)
Operating: 45% to 85%
Front panel: IEC standard IP40 (see note 2)
Terminals:
Approx. 200 g (with flush-mounting adapter)
100/110/120 VAC (common), 200/220/240 VAC (common) (See note.)
50/60 Hz (common)
90% to 110% of rated supply voltage
Approx. 2 VA
Thermocouple (with sensor burnout detection circuit), platinum resistance thermometer, or thermistor
ON/OFF or P control
Analog setting
No indication
Relay output: SPDT, 3 A at 250 VAC, resistive load (switching capacity: 330 VA)
E5C2
Thermocouple
0 to 200 (5),
0 to 300 (10),
0 to 400 (10)
32 to 392 (10),
32 to 572 (20),
32 to 752 (20)
100,000 operations min. (3 A at 110 VAC, resistive load)
IEC standard IP00
Iron vs. constantan
2
2
, 3 times each in 6 directions
, 3 times each in 6 directions
J (IC)
–50 to 50 (2),
–20 to 80 (2),
0 to 50 (1),
0 to 100 (2),
0 to 200 (5),
0 to 300 (10),
0 to 400 (10)
32 to 212 (5),
32 to 392 (10)
Platinum resistance
thermometer
Pt100
–50 to 50 (2) (6 kΩ at 0°C),
0 to 100 (2) (6 kΩ at 0°C),
50 to 150 (2) (30 kΩ at 0°C),
100 to 200 (2) (550 Ω at 200°C),
150 to 300 (2) (4 kΩ at 200°C)
---
Thermistor (see note 2)
THE

Related parts for E5C2-R20P 110'C 230VAC