MPAXD000 Red Lion Controls, MPAXD000 Datasheet - Page 30

no-image

MPAXD000

Manufacturer Part Number
MPAXD000
Description
Voltage-Current Input Module
Manufacturer
Red Lion Controls
Datasheets

Specifications of MPAXD000

Accessory Type
Analog Input Module
Signal Input Type
Selectable Voltage
No. Of Analog Outputs
5
Character Size
0.56"
Accuracy
0.03% of reading + 0.03 μA to 0.5% of reading + 0.3 μA @ 18 to 28 °C, 0.03% of reading +30 μV to 0.05% of reading +30 mV @ 18 to 28 °C, 0.05% of reading +30 Megohm to 0.05% of reading +1 Ohms @ 18 to 28 °C
Brand/series
MPAX Series
Display Type
LED
Impedance, Input
100 Ohms to 10 Kiloohms
Measuring Range
± 200 μADC to ± 2 ADC, ± 200 mVDC to ± 300 VDC, 100 Ohms to 10 Kiloohms
Resolution
10 nA to 0.1 mA, 10 μV to 10 mV, 0.01 Ohms to 1 Ohms
Standards
cULus Listed, CE Certified
Voltage, Working
85 to 250 VAC
Sealing
NEMA 4/IP65
No. Of Analog Inputs
5
Rohs Compliant
Yes
For Use With
EPAX 5 Digit Displays
Lead Free Status / RoHS Status
Lead free / RoHS Compliant
MODEL LPAX- 5 DIGIT LARGE PAX DISPLAY FOR ANALOG INPUTS
GENERAL DESCRIPTION
offering the plant floor or production area a large visual display of their current
status. Whether your measurement is temperature, weight, or flow, the LPAX
can satisfy your requirement. With the use of a units label and backlighting, the
display can be tailored to show the actual engineering unit, which further
enhances the display. This LPAX display accepts various analog inputs through
the use of input modules (MPAX) which allow the unit to adapt to most any
application. The MPAX Modules offer the same features as our highly
successful PAX Series Panel Meters. Additional plug-in option cards can add
alarms, analog output, and communication/bus capabilities, making the LPAX a
truly Intelligent Panel Meter.
SAFETY SUMMARY
corresponding literature, or on equipment, must be observed to ensure personal
safety and to prevent damage to either the instrument or equipment connected
to it. If equipment is used in a manner not specified by the manufacturer, the
protection provided by the equipment may be impaired.
DIMENSIONS In inches (mm)
The LPAX Display is a versatile display that can increase productivity by
All safety regulations, local codes and instructions that appear in this and
installation and operation of the unit.
Read complete instructions prior to
CAUTION: Risk of Danger.
4
parts of the equipment for safety purposes and must be
connected to an external protective earthing system.
The protective conductor terminal is bonded to conductive
CAUTION: Risk of electric shock.
1
SPECIFICATIONS
1. DISPLAY: 1.5" (38 mm) Red LED
2. POWER REQUIREMENTS:
3. INPUT: Accepts analog input modules, see “Selecting your display
4. ANNUNCIATORS:
5. KEYPAD: Five tactile membrane switches integrated into the front panel
6. CERTIFICATIONS AND COMPLIANCES:
! LARGE LED DISPLAY READABLE TO 70 FEET
! VARIOUS ANALOG INPUT MODULES;
! ALARMS, ANALOG OUTPUT, AND COMMUNICATION
! CUSTOM UNITS LABEL WITH BACKLIGHT
! PROGRAMMABLE USER INPUTS
! PROGRAMMABLE FUNCTION KEYS
! UNIVERSAL AC/DC POWERED MODELS
! CRIMSON PROGRAMMING SOFTWARE
! NEMA 4/IP65
Additional specifications, wiring, programming, and information for the
individual MPAX models are contained in the corresponding standard PAX
literature. This PAX literature is shipped with the ordered MPAX model.
5-Digit: (-19999 to 99999)
AC Modules: 85 to 250 VAC, 50/60 Hz, 18 VA
DC Modules: 11 to 36 VDC or 24 VAC ±10%, 50/60 Hz, 14 W
components.”
LPAX0500: MAX, MIN, TOT, SP1, SP2, SP3, and SP4
Optional units label with backlight
UL Recognized Component, File #E179259, UL61010A-1, CSA 22.2 No. 1010-1
UL Listed, File # E137808, UL508, CSA C22.2 No. 14-M95
Type 4 Enclosure rating (Face only), UL50
IECEE CB Scheme Test Certificate #US/8843/UL
ELECTROMAGNETIC COMPATIBILITY
Recognized to US and Canadian requirements under the Component
Recognition Program of Underwriters Laboratories, Inc.
LISTED by Und. Lab. Inc. to U.S. and Canadian safety standards
CB Scheme Test Report #04ME11209-20041018
IEC 61010-1, EN 61010-1: Safety requirements for electrical equipment
IP65 Enclosure rating (Face only), IEC 529
EMC specifications determined by the MPAX module.
Issued by Underwriters Laboratories, Inc.
for measurement, control, and laboratory use, Part 1.
DC VOLTAGE AND CURRENT
PROCESS SIGNALS
TRUE RMS VOLTAGE AND CURRENT
THERMOCOUPLE OR RTD
STRAIN GAGE/BRIDGE
PANEL CUT-OUT
Bulletin No. LPAX-D
Drawing No. LP0489
Released 12/05

Related parts for MPAXD000