PAXR0000 Red Lion Controls, PAXR0000 Datasheet - Page 10

Rate Counter

PAXR0000

Manufacturer Part Number
PAXR0000
Description
Rate Counter
Manufacturer
Red Lion Controls
Type
Rate Indicatorr
Datasheets

Specifications of PAXR0000

No. Of Digits / Alpha
6
Signal Input Type
Pulse
Character Size
0.56"
Ip/nema Rating
IP65 / NEMA 4X
Panel Cutout Height
1.77"
Display Font Color
Red
Panel Cutout Width
3.62"
Counter Supply Voltage
85-250VAC
Accuracy
±0.01% %
Connection Type
Cage-Clamp
Cut Out, Panel
1/8 DIN
Digit Height
0.56
Dimensions
4.2"L×3.8"W×1.95"H
Display Digit Height
0.56 "
Display Type
LED
Function
Rate Indicator
Indicator Type
Rate Meter
Number Of Digits
6
Primary Type
Electronic
Range, Measurement
0 to 99999
Special Features
Programmable Function Keys
Temperature, Operating, Range
0 to 50 °C
Termination
Cage Clamp
Voltage, Supply
85 to 250 VAC
Lead Free Status / RoHS Status
Lead free / RoHS Compliant
4.3 INPUT WIRING
4.4 SETPOINT (ALARMS) WIRING
Switch or Isolated Transistor; Current Sink
Current Sinking Output
If you are wiring Input B, connect signal to Terminal 6 instead of 5, and set DIP switches 4, 5, and 6 to the positions shown for 1, 2, and 3.
Magnetic Pickup
Current Sink Output; Quad/Direction
If using single Counter B, then wire signal to 6,
and Quad/Direction to 8. Set switch positions
4, 5, and 6 as shown for 1, 2, and 3.
Switch position is application dependent.
CAUTION: Sensor input common is NOT isolated from user input common. In order to preserve the safety of the meter application, the sensor input
SETPOINT PLUG-IN CARD TERMINALS
common must be suitably isolated from hazardous live earth referenced voltage; or input common must be at protective earth ground potential. If not,
hazardous voltage may be present at the User Inputs and User Input Common terminals. Appropriate considerations must then be given to the potential
of the user input common with respect to earth ground; and the common of the isolated plug-in cards with respect to input common.
Single Counter A
Input A
Input A
Input A
Current Sink Output; Quad/Direction
Switch or Isolated Transistor; Current Source
AC Inputs From Tach Generators, Etc.
Current Sourcing Output
User Input Jumper
in Sink Position
10
Input A
Input A
Counter A
Input A
& Rate B
SOURCING OUTPUT LOGIC CARD
SINKING OUTPUT LOGIC CARD
Shaded areas not recommended for counting applications.
Emitter Follower; Current Source
Current Sink Output; Quad/Direction
Interfacing With TTL
Two Wire Proximity, Current Source
User Input Jumper
in Sink Position
Input A
Input A
Counter A &
Counter B
Input A

Related parts for PAXR0000