BQTF2 CARLO GAVAZZI, BQTF2 Datasheet - Page 4

no-image

BQTF2

Manufacturer Part Number
BQTF2
Description
AC Tachometer/Frequency Input Module
Manufacturer
CARLO GAVAZZI
Datasheet

Specifications of BQTF2

No. Of Analog Inputs
2
For Use With
UDM Series Digital Panel Meter
UDM60
4
Output specifications (cont.)
Analogue output
Software functions
Password
Scaling parameters
Linearisation
Filter
Range
Scaling factor
Accuracy
Response time
Termperature drift
Load: 20 mA output
Insulation
Pulse per revolution
Input engineering unit
Scaling
Points
Range
Operating range
Filtering coefficient
10 V output
(on request)
Module: BO AV
0 to 20 mADC, 0 to 10 VDC
Programmable within the
entire retransmission range;
allows to manage the
retransmission of all the
values from
0 to 20 mA / 0 to 10V
± 0.2% FS (@ 25°C ± 5°C)
≤ 10 ms
± 200 ppm/°C
≤ 700 Ω
≥ 10 kΩ
By means of opto-couplers
4000V
measuring input
4000 V
power supply input
Numeric code max 4 dgt
2 levels of data protection.
1st level 0 to 4999 com-
pletely protected. 2nd level
5000 to 9999 access to
programming is protected,
while alarm set-points are
directly programmable
from the measuring mode.
Programmable and inde-
pendent per each channel
(only in case of dual fre-
quency meter), from 1 to
9999.
Programmable among Hz,
kHz, rpm, krpm, rph, krph,
and independent per each
channel (only in case of
dual frequency meter).
Selection of the decimal
point, min value and max
value of the input range
(expressed in engineering
units). Selection of the dec-
imal point, min value and
max value of the displayed
range correspondent to the
input range.
Programmable and inde-
pendent per each channel
(only in case of dual fre-
quency meter).
Up to 16
Input value and displayed
value of each point within
the programmable input
and display range
0 to 100% of the displayed
value of channel A
1 to 32
RMS
RMS
output to
output to
Specifications are subject to change without notice
Excitation output
Operating modes
Displayed values
Min max storage
Setpoint modification
Latch alarm reset
Counter reset
Analogue indicators
Diagnostic
UdmSoft
Notes:
Isolation
Filter action
Overflow/Underflow
Display over range
Electrical full scale or overload
measuring input
4000V
power supply input
The two outputs cannot be
used at the same time.
8.2 VDC ±10%, max 10mA
13 VDC ±10%, max 40mA
25 Vrms between aux.
output and measuring
inputs 4000 V
aux. output and the other
input/outputs
output, analogue output
See “list of selectable func-
tions and variables”
See “list of selectable func-
tions and variables”
Automatic storage (in the
EEPROM) of the minimum
and maximum measured
values from the previous
memory reset
Direct access to the set-
point modification from the
measuring mode (if allowed
by the selected password).
Direct access to the reset
from the measuring mode.
Direct access to the reset
from the measuring mode.
11 positions (9 values
between the minimum dis-
play value and the max-
imun display value, under-
flow and overflow) or
speed rotation direction.
flow or underflow position
“Err” indication
Software for programming
UDM60 by means of PC
(Windows 95, 98se, ME,
XP) by means of serial port
RS485 and relevant con-
nection cable. The soft-
ware is available in English,
Spanish, Italian, German,
French. See also “Pro-
gramming of UDM60 by
means of PC”.
On measurements, serial
Analogue indicator over-
“EEE” indication
UDM60 DS ENG 261110
RMS
output to
RMS
between