CJ1W-PNT21 Omron, CJ1W-PNT21 Datasheet - Page 119

no-image

CJ1W-PNT21

Manufacturer Part Number
CJ1W-PNT21
Description
CJ Profinet Master
Manufacturer
Omron
Datasheet

Specifications of CJ1W-PNT21

Lead Free Status / Rohs Status
Lead free / RoHS Compliant
Service Code
For normal completion, the value when the left-most bit of the service code specified in the command turns ON
is stored as shown in the following table.
/i
When an error response is returned for an explicit message, the value is always 94 Hex.
Data
Read data is included only when a read command is executed.
Error Codes
The explicit message error codes as listed in the following table.
/i
106
Function
Write data
Read data
Reset
Save
Response
code
08FF
09FF
16FF
15FF
13FF
0CFF
20FF
0EFF
10FF
14FF
19FF
2AFF
Error name
Service not supported
Invalid Attribute value
Object does not exist
Too much data
Not enough data
Object state conflict
Invalid parameter
Attribute not settable
Device state conflict
Attribute not supported
Store operation failure
Group 2 only server
general failure
Command service code
10 Hex
0E Hex
05 Hex
16 Hex
Cause
The Service code is incorrect.
The specified Attribute value is not supported.
The data written was outside valid range.
The specified Instance ID is not supported.
The data is larger than the specified size.
The data is smaller than the specified size.
The specified command cannot be executed
due to an internal error.
The specified operation command data is not
supported.
An Attribute ID supported only for reading has
been executed for a write service code.
The specified command cannot be executed
due to an internal error.
The specified Attribute is not supported.
The data cannot be stored in memory.
The specified command or Attribute is not
supported or the Attribute was not set.
Response service code
90 Hex
8E Hex
85 Hex
96 Hex

Related parts for CJ1W-PNT21