Troubleshooting using the IO Controller indicators
6-2-3
78
OFF
ON
(green)
ON
(green)
ON
(green)
ON
(green)
ON
(green)
Unit errors
Error category
MS
OFF
OFF
Flashing
(green)
Flashing
(green)
Flashing
(green)
ON
(green)
NS
Troubleshooting Errors Occurring in the IO Controller Unit
Indicator status
Startup errors
OFF
OFF
OFF
ON
(yellow)
ON
(yellow)
ON
(yellow)
COMM 100M
OFF
OFF
OFF
OFF
ON
(yellow)
ON
(yellow)
Error
/i
On smaller PROFINET IO Networks the sequence from starting the
PROFINET IO core software to being in full Data Exchange with all the IO
Devices can be very fast that the individual steps can not be distinguished.
Unit errors are errors which occur at starting or normal operation of the system
and which prevent the Unit from functioning correctly in the PLC system.
Usually these errors also cause the CS/CJ PLC CPU ERR/ALM indicator to be
lit or flashing. For more information on error indications in the PLC, refer to the
CS1 Series CPU Unit Operation Manual (W339) or the CJ Series CPU Unit
Operation Manual (W393) for more details.
Unit errors
/i
- -
r
dot flashing
r
dot flashing
r
dot ON
r
dot ON
r
dot ON
7-segment
Booting and initializing with the
PLC
Valid configuration detected
PROFINET IO core software
started
Relations to PROFINET IO
Devices are set up
Data Exchange with at least one
IO Device
Data Exchange with at all
configured IO Devices
Network/Unit status
1 to 6
7-segment
ON (red)
Indicators
MS
OFF
The PROFINET IO Configuration
Bootup and initialization with the
PLC in progress.
Restart the PROFINET IO
Controller unit if this status
continues for an extended period
of time. Replace the CPU Unit
and/or PROFINET IO Controller
Unit if the problem is not corrected
by restarting.
downloaded from the configuration
tool is evaluated during startup of
the unit.
The PROFNET IO Controller has
started its core communciation
software and is ready to start
communciation with PROFINET
IO Devices.
Before PROFINET IO
Communication is fully running a
relation between each IO Device
and the IO Controller is
esthablished.
At least one IO Device is
exchanging IO Data with the IO
Controller
All configured IO Devices are
detected by the IO Controller and
to all IO Data Exchange is
esthablised.
NS
--
Error log
Comments
(Hex)
Section 6-2