Voltage Regulator/Power Conditioner

63-23-710-8

Manufacturer Part Number
63-23-710-8
Description
Voltage Regulator/Power Conditioner
Manufacturer
SOLA HEVI DUTY
Series
MCRr
Datasheets

Specifications of 63-23-710-8

Suppressor Type
Power Line Conditioner
Input Voltage
415VAC
Output Voltage
110V
Width
228.6mm
Height
457.2mm
Output Voltage 3
220V
Output Type
Fixed
External Height
18"
Output Power
1000 VA
Input Voltage (nominal)
380 V
Features
Harmonic Filtering
Mounting Type
Surface Mount
Voltage Regulation
+/- 3 %
Voltage Regulation Accuracy
+/- 3 %
Lead Free Status / RoHS Status
Lead free / RoHS Compliant
6.12 Operating Temperature
Standard units are designed to operate in ambient temperatures of -20°C to
+40°C. In operation, a temperature rise will occur whether or not the transformer
is serving load. Normally, this rise may fall anywhere in the range of 45°C to
110°C, depending on the regulator type and rating. In any case, the maximum
operating temperature at an ambient of +40°C is always within safe operating
limits for the class of insulating material used.
6.13 Effect of Temperature
The output voltage will show a small change as the unit warms up to stable
operating temperatures at a constant ambient temperature. This change may be
about one or two percent, depending on the unit’s VA rating. At a stable oper-
ating temperature, the output voltage will change slightly with varying ambient
temperature. This shift is approximately one percent for each 40°C of tempera-
ture change.
7.0 Service & Maintenance
The unit is a simple, rugged device with no moving parts. Routine service and/or
maintenance is not required. In cases of poor performance, please refer to “8.0
Troubleshooting” or contact SolaHD Technical Support for assistance.
7.1 Field Replacement of Capacitors
Capacitors used in all regulators are the highest commercial grade, with each
one given a rigid acceptance test upon receipt. Nevertheless, as with all capaci-
tors, there is a small percentage of failure. SolaHD guarantees free replacement
at the factory of any capacitors which fail within one year of sale. Older units can
be replaced at moderate charge.
Where technical help is available, it may be possible to test and identify defec-
tive capacitors in the field. Factory advice and cooperation must be requested in
advance.
MCR Portable Series Instruction Manual • 9