Technical specifications
The specifications of the instrument are verified using the “implementation verification”
table 3 as specified in IEC 61000-4-30 2002 Chapter 6.2. Accuracy is specified in % of
reading unless otherwise specified. Specifications are valid for models Fluke 435 and
Fluke 434 unless otherwise specified.
Input characteristics
Display modes
6 Fluke Corporation Fluke 430 Series Three-Phase Power Quality Analyzers
Voltage inputs
Number of inputs
Maximum input voltage
Nominal voltage range
Maximum peak measurement voltage
Input impedance
Bandwidth
Scaling
Current inputs
Number of inputs
Type
Range
Input impedance
Bandwidth
Scaling
Nominal frequency
Sampling system
Resolution
Maximum sampling speed
RMS sampling
PLL synchronization
Waveform display
Phasor
Meter readings
AutoTrend graph
Bargraph
Event list
4 (3 phases + neutral) dc-coupled
1000 Vrms
50 V to 500 V according IEC 61000-4-30. Selectable from 1 V to 1000 V.
6 kV
4 MΩ//5 pF
> 10 kHz, up to 100 kHz for transient display
1:1, 10:1, 100:1, 1000:1 and variable
4 (3 phases + neutral) dc-coupled
Clamp on current transformer with mV output
1 Arms to 400 Arms with included clamps (i400s/Fluke 434)
30 A to 3000 Arms with included clamps (i430-flex/Fluke 435)
1 Arms to 3000 Arms with optional clamps
50 kΩ
> 10 kHz
0.1, 1, 10, 100, 1000 mV/A, variable, i5s and i430-flex
40 Hz to 70 Hz
16 bit analog to digital converter on 8 channels
200 kS/s on each channel simultaneously
5000 samples on 10/12
4096 samples on 10/12
Available in Scope and Transient mode
Captures 8 waveforms simultaneously
Display update rate 5x per second
Up to 10/12
Cursors: single vertical line showing min, max, avg reading at cursor position
Shows real time phasor diagram
Available in Scope and Unbalance mode
Display update rate 5x per second
Available in Volts/Amps/Hertz, Harmonics, Power and Energy, Flicker, Unbalance and Logger
Available in Volts/Amps/Hertz, Dips and Swells, Harmonics, Power and Energy, Flicker, Unbalance, Inrush,
Mains Signaling
Cursors: single vertical line showing with min, max, avg reading at cursor position
Available in Harmonics and Monitor mode
Available in Dips and Swells, Mains Signaling
2
times horizontal zoom
4
Logger
2
2
4
cycles according IEC 61000-4-30
cycles according IEC 61000-4-7
and Monitor mode
4
, Logger
4
and Monitor mode
4
mode