MA10/D/2 MTL SURGE TECHNOLOGIES, MA10/D/2 Datasheet

Power Line Filter/Suppressor

MA10/D/2

Manufacturer Part Number
MA10/D/2
Description
Power Line Filter/Suppressor
Manufacturer
MTL SURGE TECHNOLOGIES
Datasheet

Specifications of MA10/D/2

Filter Type
RFI
Current Rating
10A
Voltage Rating
240V
Leakage Current Max
0.3mA
Termination Type
Screw
Width
79mm
Height
93mm
Depth
25mm
Mounting Type
DIN Rail
MA05/10 Series
Unique units combining filtering, surge protection and ring
suppression for protection against the effects of electrical
disturbances on ac power cabling
Telematic’s MA05 and MA10 Series
protects electronic equipment and computer
networks against the effects of ‘noise
pollution’ induced in mains power supplies.
A unique combination of circuit elements
‘cleans up’ the effects of industrial noise
and surges caused by lightning, switching
devices, thyristor controls, transmission
system overloads and power-factor correction
circuits.
The units are available in alternative
versions – ‘SC’ suffixed models housed in
standard filter ‘cans with connections via
safety-shrouded
‘Standard’ I units for wall or floor mounting
in a plastic enclosure with screw terminals
inside; or ‘D’ suffixed units for G- or Top-hat
section DIN-rail mounting. The ‘SC’ and ‘I’
units are useful for OEM incorporation into
packaged systems as a superior alternative
to conventional filters and also for retro-
fitting to existing systems. The ‘D’ type
units are ideally suited to protecting panel-
mounted equipment.
Combines high quality filtering with ‘ring’
suppression
Three different packages available,
Wall/floor mounted (I)
DIN-rail mounted (D)
Standard filter case (SC)
Added thermal fuse protection
Unique design for EMC compliance –
exceeding IEC61000–4–5, level 4
spade
terminations’;
With a unique ‘three-stage’ combination
of protection elements, these units
suppress conducted RFI and voltage
surges. The circuit elements are; first,
surge clipping components to absorb
transient surges that may otherwise
damage equipment; second, a filter to
suppress noise in the system; and third,
‘ring’ suppression.
prevents surges causing the filter to ‘ring’
(oscillate) under low load conditions –
an effect that actually accentuates
interference in most commercially
available filters. The ‘Transient response’
graph printed overleaf illustrates the
typical output response of an MA10/D
when a 6kV, 3kA standard 8/20µs surge
is applied to the input.
The MA05 and MA10 devices
operate in both signal
directions
therefore reduce
both electro-
magnetic
AC Power/EMC
and
The third of these
Protection
emissions and the susceptibility of the
associated equipment to emissions from
other sources. Thermal fusing is also
incorporated into each device as an
additional safety feature.
Manufactured in accordance with
ISO9001, the performance of all units is
tested before despatch and exceeds the
requirements of IEC 61000-4-5, level 4.
Since MA05/10 devices suppresss
conducted RFI and voltage surges they
enable associated equipment to comply
with this aspect of the European
‘CE’ mark standards.

Related parts for MA10/D/2

MA10/D/2 Summary of contents

Page 1

MA05/10 Series Unique units combining filtering, surge protection and ring suppression for protection against the effects of electrical disturbances on ac power cabling Combines high quality filtering with ‘ring’ suppression Three different packages available, Wall/floor mounted (I) DIN-rail mounted (D) ...

Page 2

MA05/10 EMC/Surge Protection Devices Guide to applications and selection Industrial Control Systems Industrial control systems utilising programmable logic controllers (plc) and industrial computers are particularly vulnerable due to the aggressive electrical environments for which they are intended, such as process ...

Page 3

Computer/OEM Equipment Increased reliance on computers in industry and the workplace, coupled with an increasingly ‘noisy’ electrical supply and a higher incidence of lightning activity has led to a higher risk of costly system downtime and disruption. In turn, this ...

Page 4

... MA05/D/1 ‘DIN-rail’ version, 110V, 5Amp MA10/D/1 ‘DIN-rail’ version, 110V, 10Amp MA05/D/2 ‘DIN-rail’ version, 240V, 5Amp MA10/D/2 ‘DIN-rail’ version, 240V, 10Amp MA05/I/1 Wall/floor mounting version, 110V, 5Amp MA10/I/1 Wall/floor mounting version, 110V, 10Amp ...

Related keywords