CJ1W-AD04U Omron, CJ1W-AD04U Datasheet - Page 9

no-image

CJ1W-AD04U

Manufacturer Part Number
CJ1W-AD04U
Description
Isolated Universal Analog 4pt
Manufacturer
Omron
Datasheet

Specifications of CJ1W-AD04U

Lead Free Status / Rohs Status
Lead free / RoHS Compliant
Loop-control CPU Units
Loop Controller Element Specifications
Model
Operation method
Loop Controller element
Function
block analog
operations
Sequence
control
I/O blocks
Method for creating and transferring function blocks
External I/O response time
Operation cycle
Internal operation
Control method
Alarms
Control and
operation
blocks
Step ladder
program
blocks
Field terminal
blocks
User link
tables
HMI function I/O function for the speci-
System
Common
block
Item
PID and other control
functions, square root op-
eration, time operations,
pulse train operation, and
other operation functions
for various processes.
Logic sequence and step
sequence functions
Analog I/O function with
Analog I/O Unit, contact
I/O function with Basic I/O
Unit
Analog data I/O and con-
tact data I/O function for
CPU Unit
fied bank of the EM Area
in the CPU Unit for func-
tion block ITEM data used
for Control, Operation,
External Controller, and
System Common blocks
for the HMI function.
System common opera-
tion cycle setting, run/
stop command, load rate
monitor, etc.
Number of control loops
PID control method
Control combinations
PID block internal alarms 4 PV alarms (upper upper-limit, upper limit, lower limit, lower lower-limit) and 1
Alarm blocks
CJ1G-CPU42P
Function block method
LCB01
50 blocks max.
20 blocks max.
2,000 commands total
100 commands max. per block
Separable into 100 steps max.
30 blocks max.
2,400 data items max.
Allocated 1 EM Area bank
Operation and Control blocks:
50 blocks max. × 20 send/receive words
System Common blocks:
20 send/receive words
Single block
Created using CX-Process Tool (purchased separately) and transferred to Loop
Controller.
The time from external input of analog signals up to external output of analog signals
on a single control loop depends on the function block's operation cycle and the
CPU Unit's cycle time.
0.01, 0.02, 0.05, 0.1, 0.2, 0.5, 1, or 2 s (default: 1 s) (See note.)
Can be set for each function block.
Note: 0.01, 0.02, and 0.05 s cannot be set for some blocks.
• The maximum number of loops that can be used if the LCB load rate is 80% for a
Note: Loop Controller element LCB01: 25 loops max.
PID with 2 degrees of freedom
Any of the following function blocks can be combined:
Basic PID control, cascade control, feed-forward control, sample PI control, Smith
dead time compensation control, PID control with differential gap, override control,
program control, time-proportional control, etc.
deviation alarm per PID block
High/low alarm blocks, deviation alarm blocks
standard applications (e.g., with each loop consisting of one Ai4 Terminal, Seg-
ment Linearizer, Basic PID, and A04 terminal) is shown in the following table.
0.01 s
0.02 s
0.05 s
0.1 s
Operation
cycle
20 loops
35 loops (see note) 0.5 s
70 loops (see note) 1 s
100 loops (see note) 2 s
Maximum number
of loops
Specifications
Loop Controller Element Specifications
CJ1G-CPU43/44/45P(-GTC)
LCB03
300 blocks max.
200 blocks max.
4,000 commands total
100 commands max. per block
Separable into 100 steps max.
CJ1G-CPU43P: 30 blocks max.
CJ1G-CPU44/45P: 40 blocks max.
Allocated 1 EM Area bank
Operation and Control blocks:
300 blocks max. × 20 send/receive words
System Common blocks:
20 send/receive words
0.2 s
Operation
cycle
150 loops
(See note.)
Maximum number
of loops
11