DRT2-MD16S Omron, DRT2-MD16S Datasheet - Page 442

no-image

DRT2-MD16S

Manufacturer Part Number
DRT2-MD16S
Description
DRT2 Mix IO E-Con8 In/out, NPN
Manufacturer
Omron
Datasheet

Specifications of DRT2-MD16S

Lead Free Status / Rohs Status
Lead free / RoHS Compliant
Temperature Zone
Counter Function
(Zone Count)
Temperature Input Terminals
Counting starts when this
temperature is exceeded.
When the temperature zone is set
to 10 ° C above the set temperature
(95 ° C), the function counts how
long the temperature is within that
10 ° C zone.
5. To set the OFF delay function, input the desired value in the Comparator
6. Return to the General Tab, click the Download Button, and then click the
7. Click the OK Button and exit the window.
This function times (in 1-second units) how long the temperature input value is
within a user-set temperature range. The zone count can indicate when pre-
ventative maintenance is required for devices or applications that deteriorate
at a fixed rate within the user-set temperature range.
Select the temperature zone settings in the Comparator Tab. The tempera-
ture zone boundaries are defined by the High High Limit (HH), High Limit (H),
Low Low Limit (LL), or Low Limit (L). Any threshold value can be set in the
Threshold Zone Counter to indicate when the threshold time within the zone
has been exceeded.
The Over Threshold status can be read in the Maintenance Information Win-
dow or via an explicit message.
85°C
Temperature
Off Delay field.
Reset Button to reset the Unit.
Counting
starts
10°C
Counting
stops
Counting
starts
Time
Section 7-6
421