H3DS-SL AC24-230/DC24-48 Omron, H3DS-SL AC24-230/DC24-48 Datasheet - Page 30

17.5mm TIMER DIN. MNT.

H3DS-SL AC24-230/DC24-48

Manufacturer Part Number
H3DS-SL AC24-230/DC24-48
Description
17.5mm TIMER DIN. MNT.
Manufacturer
Omron
Series
H3DSr
Datasheets

Specifications of H3DS-SL AC24-230/DC24-48

Relay Type
Integrated
Function
Programmable (Multi-Function)
Circuit
SPDT (1 Form C)
Delay Time
0.1 Sec ~ 120 Hrs
Output Type
Mechanical Relay
Contact Rating @ Voltage
5A @ 250VAC
Voltage - Supply
24 ~ 230VAC, 24 ~ 48VDC
Mounting Type
DIN Rail
Termination Style
Screw Terminal
Timing Adjustment Method
Screwdriver Slot
Timing Initiate Method
Input Voltage, Trigger Signal
Timing Range
0.1 s to 120 Hrs
Supply Voltage
24 V to 230 V
Lead Free Status / RoHS Status
Lead free / RoHS Compliant
Lead Free Status / RoHS Status
Lead free / RoHS Compliant
Other names
H3DSSLAC24230DC2448
Z2395
H3DS-G
I
Note: For reference:
Accuracy of operating
time
Setting error
Total tolerance of transfer
time
Influence of voltage
Influence of temperature
Insulation resistance
Dielectric strength
Impulse withstand voltage 3 kV (between power supply terminals)
Noise immunity
Static immunity
Vibration resistance
Shock resistance
Life expectancy
EMC
Case color
Degree of protection
Weight
Characteristics
A maximum current of 0.15 A can be switched at 125 VDC (cos φ = 1).
A maximum current of 0.1 A can be switched if L/R is 7 ms.
In both cases, a life of 100,000 operations can be expected.
The minimum applicable load is 10 mA at 5 VDC (failure level: P).
± 1% max. of FS
± 10% ± 50 ms max. of FS
± (25% FS + 5 ms) max.
± 0.5% max. of FS
± 2% max. of FS
100 M Ω min. at 500 VDC
Between current-carrying metal parts and exposed non-current-carrying metal parts:
2,000 VAC (50/60 Hz) for 1 min.
Between control output terminals and operating circuit: 2,000 VAC (50/60 Hz) for 1 min.
Between contacts not located next to each other: 1,000 VAC (50/60 Hz) for 1 min.
4.5 kV (between current-carrying metal parts and exposed non-current-carrying metal parts)
Square-wave noise generated by noise simulator (pulse width: 100 ns/1 µ s, 1-ns rise) ± 1.5 kV
Malfunction: 4 kV
Destruction: 8 kV
Malfunction: 0.5-mm single amplitude at 10 to 55 Hz
Destruction: 0.75-mm single amplitude at 10 to 55 Hz
Malfunction: 200 m/s
Destruction: 300 m/s
Mechanical: 10 million operations min. (under no load at 1,800 operations/h)
Electrical: 100,000 operations min. (5 A at 250 VAC, resistive load at 360 operations/h)
(see note)
(EMI)
Emission Enclosure: EN55011 Group 1 class B
Emission AC Mains: EN55011 Group 1 class B
(EMS)
Immunity ESD: EN61000-4-2:6 kV contact discharge (level 3)
Immunity RF-interference from AM Radio Waves: EN61000-4-3: 10 V/m (80 MHz to 1 GHz) (level 3)
Immunity Burst: EN61000-4-4: 2 kV power port and output port (level 3)
Immunity Surge: EN61000-4-5: 2 kV common mode (level 3)
Light gray (5Y7/1)
IP30 (IP20 for terminal block)
Approx. 70 g
8 kV air discharge (level 3)
1 kV control port with capacitive clamp (level 3)
1 kV differential mode (level 3)
2
2
, 3 times each in 6 directions
, 3 times each in 6 directions
H3DS-G