H3DS-SL AC24-230/DC24-48 Omron, H3DS-SL AC24-230/DC24-48 Datasheet - Page 49

17.5mm TIMER DIN. MNT.

H3DS-SL AC24-230/DC24-48

Manufacturer Part Number
H3DS-SL AC24-230/DC24-48
Description
17.5mm TIMER DIN. MNT.
Manufacturer
Omron
Series
H3DSr
Datasheets

Specifications of H3DS-SL AC24-230/DC24-48

Relay Type
Integrated
Function
Programmable (Multi-Function)
Circuit
SPDT (1 Form C)
Delay Time
0.1 Sec ~ 120 Hrs
Output Type
Mechanical Relay
Contact Rating @ Voltage
5A @ 250VAC
Voltage - Supply
24 ~ 230VAC, 24 ~ 48VDC
Mounting Type
DIN Rail
Termination Style
Screw Terminal
Timing Adjustment Method
Screwdriver Slot
Timing Initiate Method
Input Voltage, Trigger Signal
Timing Range
0.1 s to 120 Hrs
Supply Voltage
24 V to 230 V
Lead Free Status / RoHS Status
Lead free / RoHS Compliant
Lead Free Status / RoHS Status
Lead free / RoHS Compliant
Other names
H3DSSLAC24230DC2448
Z2395
Specifications
I
Note: Can be mounted to 35-mm DIN Track with a plate thickness of 1 to 2.5 mm.
I
Note: When the time setting dial is set to “0” for any time scale,
I
Note: DC ripple rate: 20% max.
H3DS-X
2
Item
Operating mode
Operating/Reset method
Output type
External connections
Terminal block
Terminal screw tightening torque
Output type
Mounting method
Attachment
Approved standards
Time scale
0.1 s
1 s
0.1 m
1 m
0.1 h
1 h
10 h
Rated supply voltage (see note)
Operating voltage range
Power reset
Reset voltage
Reset current
Power consumption
Control output
Ambient temperature
Ambient humidity
General
Time Ranges
Ratings
the output will operate instantaneously.
H3DS-X
ON-delay
Time-limit operation/self-resetting
SCR output
Screw terminal, cage clamp
Screw terminal type: Clamps two 2.5-mm
Cage clamp type: Clamps two 1.5-mm
0.98 N • m max.
(Star operation circuit) Relay: SPST-NO
(Delta operation circuit) Relay: SPST-NO
DIN track mounting (see note)
Nameplate label
UL508, CSA C22.2 No.14
Conforms to EN61812-1, IEC60664-1 (VDE0110) 4 kV/2, VDE0106/P100
Star operation time ranges
0.1 to 1.2 s
1 to 12 s
0.1 to 1.2 min
1 to 12 min
0.1 to 1.2 h
1 to 12 h
10 to 120 h
24 to 230 VAC/VDC (50/60 Hz)
85% to 110% of rated supply voltage
Minimum power-off time: 0.1 s
1.0 VAC/VDC max.
5 mA max.
5 mA max.
SCR output: 5 mA to 0.7A
Operating: –10 ° ° ° ° C to 55 ° ° ° ° C (14 ° ° ° ° F to131 ° ° ° ° F) with no icing
Storage: –25 ° ° ° ° C to 65 ° ° ° ° C (–13 ° ° ° ° F to 145 ° ° ° ° F) with no icing
Operating: 35% to 85%
2
max. bar terminals without sleeves.
2
max. bar terminals without sleeves.
H3DS-X

Related parts for H3DS-SL AC24-230/DC24-48