FNP600-48G POWER ONE, FNP600-48G Datasheet - Page 4

no-image

FNP600-48G

Manufacturer Part Number
FNP600-48G
Description
Linear & Switching Power Supplies Front End 600W (48V)
Manufacturer
POWER ONE
Datasheet

Specifications of FNP600-48G

Input Voltage
90 to 264V
Output Voltage
48V
Number Of Outputs
1
Output Power (max)
600W
Input Frequency
47 to 63Hz
Screening Level
Commercial
Product Length (mm)
298.2mm
Product Height (mm)
40.6mm
Product Depth (mm)
83.8mm
Operating Temperature Min Deg. C
0C
Operating Temperature Max Deg. C
70C
Mounting Style
Desktop
Product
Switching
Lead Free Status / RoHS Status
Compliant
Lead Free Status / RoHS Status
Compliant
Control and Monitoring
I
BCD20034-G Rev. AD, 11-May-10
2
2
1
C Bus Management Interface
Static
Status
(Logic 1 or 0)
Real-Time Monitoring
Control Signals
Also available on I
A pull-up to 3.3V can be achieved by terminating the logic signal with a 10 kΩ resistor to logic ground.
DC OK
Input Power Fail Warning
Power Supply Present
Signal
Current Share
Remote Sense
Output Enable
2
C data line.
Parameter
Includes static information such as: part number and revision level, output rating, serial number, date code,
and manufacturing location.
Power Supply OK.
AC Input OK.
DC Output OK.
Power Supply Seated.
Overtemperature.
Overcurrent.
Fan OK.
Output voltage (main output) 0.1V LSD.
Output current (main output) 0.1A LSD.
Time in service.
Enable for main output.
Output voltage to: (0.01V resolution on 12V supplies;
0.05V resolution on all 48V supplies).
Fan speed level.
FNP600-12:
FNP850-12:
FNP600-48:
FNP1000-48:
& FNR-5-12G/FNR-5-48G Power Shelves Data Sheet
TTL open-collector signal with active
20-mA pull-down. Represents percent
of output voltage where signal is OK.
Below this voltage, a signal high
condition indicates an output which is
out of tolerance. Green DC OK LED on
front panel indicates normal operation.
Internally pulled up to 5V with a 5.1 kΩ
resistor. Note.
TTL open-collector signal with active
20-mA pull-down. High indicates an
input power fail. Power Fail Warning
will turn OFF green AC OK LED.
Represents the time after warning
signal before Vout drops to 95% due to
loss of input power.
up to 5V with a 5.1 kΩ resistor. Note.
Resistance of connection to logic
ground which allows user to determine
if power supply is present.
Main output only. Difference in current
between two supplies at >10% load
value.
Total voltage compensation for cable
losses with respect to the main output.
Open circuit or logic high from ENA pin
to Vo1 RTN shuts OFF Vo1; Vaux and
fan are operational. Logic low (2 mA
sink capability) or jumper will turn ON
Vo1 within 500 ms. Open circuit
voltage on enable pin is 3.3 VDC.
Externally applied voltage to the enable
pin should NOT exceed 7 VDC. Signal
is referred to as Logic Return (LRTN).
Page 4 of 15
Conditions/Description
FNP600/850/1000 AC-DC Front-Ends
2
1
Internally pulled
1
2
1
Min.
90
5
Nom.
10
www.power-one.com
Max.
110
0.5
5
7
2
2
Units
ms
%
A
V