Description
Controller, Digital Temp, 96x96mm, Relay Out, Thermoc In, 100-240VAC, 3Aux Out
Manufacturer
Omron Automation
Type
Temperaturer
Datasheet

Specifications of E5ANR3MT500NAC100240

Brand/series
E5AN Series
Communication
USB
Contact Form
SPST-NO
Dimensions
96mmW×96mmH×78mmD
Enclosure Rating
IP00, IP20, IP66
Input Type
RTD/Thermocouple
Ip Rating
IP00, IP20, IP66
Mounting Type
DIN Rail
Number Of Outputs
4
Output Type
Relay
Primary Type
Controller
Special Features
USB Serial
Standards
UL, cULus, CSA
Termination
Terminal Block
Voltage, Supply
100 to 240 VAC
Supply Voltage
100-240 VAC or 24 VAC/VDC
Current Output
4-20 mA DC (E5CN-E5AN-E5EN)
Thermocouple Inputs
K, J, T, L, E, U, N, R, S, B
Platinum Rtd
Pt100 and JPt100
Infrared Sensor
10-70°C, 60-120°C, 115-165°C, 160-260°C
Voltage
0 to 50 mV
Lead Free Status / Rohs Status
RoHS Compliant part
18
E5AN/E5EN
Lineup
Note: Models with one control output or two control outputs can be used for heating/cooling control.
Model Number Structure
Model Number Legend
Controllers
1. Control Output 1
2. Auxiliary Outputs
3. Heater Burnout/SSR Failure, Control Output 2, or External
4. Option
5. Input Type
6. Power Supply Voltage
7. Case Color
8. Terminal Cover
9. Version
E5AN/E5EN-@3@M@@-@-500-N
R: Relay output
Q: Voltage output (for driving SSR)
C: Current output
3: Three outputs
Power Supply for ES1B
Blank: None
Q: Control output 2 (voltage output for driving SSR)
Y: Long-life relay output (hybrid)
H: Heater burnout/SSR failure/Heater overcurrent detection (CT1)
HH: Heater burnout/SSR failure/Heater overcurrent detection
P: Power supply for sensor
M: Option Unit can be mounted.
T: Universal thermocouple/platinum resistance thermometer input
L: Analog current/voltage input
Blank: 100 to 240 VAC
D: 24 VAC/VDC
Blank: Black
W: Silver
-500: With terminal cover
N: Available only to models released after January 2008.
E5AN/E5EN
Basic Type
(CT2)
1 2 3 4 5 6
Terminal block
7
8
9
Temperature input
Analog input
Option Units
1. Function
E53-@
EN01: RS-232C communications
EN03: RS-485 communications
AKB: Event input
1
2 control outputs
2 control outputs
1 control output
1 control output
3 auxiliary outputs
3 auxiliary outputs
3 auxiliary outputs
3 auxiliary outputs