CJ1W-PA202 Omron, CJ1W-PA202 Datasheet - Page 4

no-image

CJ1W-PA202

Manufacturer Part Number
CJ1W-PA202
Description
POWER SUPPLY 100-240VAC
Manufacturer
Omron
Datasheet

Specifications of CJ1W-PA202

Lead Free Status / Rohs Status
Lead free / RoHS Compliant
Other names
CJ1W-PA202
CJ1WPA202
Z3157
*1. Disconnect the Power Supply Units LG terminal from the GR terminal when testing insulation and dielectric strength. Testing the insulation and
*2. Supported only when mounted to CPU Rack.
*3. The inrush current is given for a cold start at room temperature. The inrush control circuit uses a thermistor element with a low-temperature
*4. Maintain an ambient storage temperature of −25 to 30°C and relative humidity of 25% to 70% when storing the Unit for longer than 3 months
*5. Change the applied voltage gradually using the adjuster on the Tester. If the full dielectric strength voltage is applied or turned OFF using the
*6. CJ1W-PD022 is not insulated between the primary DC power and secondary DC power.
*7. Internal components in the Power Supply Unit will deteriorate or be damaged if the Power Supply Unit is used for an extended period of time
External Interface
CJ1W-PA205R
CJ1W-PA205C
CPU Rack
dimensions
Safety measures
Power Supply Unit
Terminals
external connect
dielectric strength with the LG terminal and the GR terminals connected will damage internal circuits in the CPU Unit.
current control characteristic. If the ambient temperature is high or the PLC is hot-started, the thermistor will not be sufficiently cool, and the
inrush currents given in the table may be exceeded by up to twice the given values. When selecting fuses or breakers for external circuits,
allow sufficient margin in shut-off performance.
to keep the replacement notification function in optimum working condition.
switch on the Tester, the generated impulse voltage may damage the Power Supply Unit.
exceeding the power supply output capacity or if the outputs are shorted.
PA205R
AC input
Item
POWER
GR
LG
POWER Indicator
Lit when 5 V are being output from the Power Supply Unit.
AC100-240V
OUTPUT
AC240V
DC24V
NC
NC
INPUT
AC100-240V
INPUT
L2/N
90.7 to 466.7 × 90 × 65 mm (W × H × D) (not including cables)
Note: W = a + b + 20 × n + 31 × m + 14.7
Conforms to cULus and EC Directives.
L1
RUN
L2/N
L1
CJ1W-PA205R
a: Power Supply Unit: PA205R and PA205C = 80; PA202 = 45; PD025 = 60; PD022=27
b: CPU Unit: CJ1-H or CJ1 = 62; CJ1M-CPU1@ = 31; CJ1M-CPU2@ = 49
The total width is given by the following: W = 156.7 + n × 20 + m × 31, where n is the number of 32-point I/O Units or I/O Control Units
and m is the number of other Units.
ALARM
OUTPUT
DC30V,50mA
NORMAL:ON
ALARM :OFF
CJ1W-PA205C
Replacement notification display
L
+
AC input
LG
GR
RUN output
TEST
POWER
Years
CJ1W-PA205C
POWER indicator
Lit: 5-V output from Power Supply Unit.
TEST switch
The TEST switch can be used to
temporarily turn OFF the alarm output
that notifies when replacement is
needed.
Alarm output
(replacement notification output)
External connection terminals
Specifications
CJ1W-PA202
CJ1W-PD025
CJ1W-PA/PD
CJ1W-PD022
4