200-JC6DT3 MTU Onsite Energy, 200-JC6DT3 Datasheet
200-JC6DT3
Related parts for 200-JC6DT3
200-JC6DT3 Summary of contents
Page 1
... DIESEL ENGINE-GENERATOR SET 200-JC6DT3 200 ekW / Standby / / 180 ekW 60 Hz Prime 208 - 600V SySTEm RATINGS Standby Voltage (L-L) 240V** Phase 200 kVA 200 AMPS 833 skVA@30% Voltage Dip 250 Generator Model* 432CSL6212 Temp Rise 130°C/27°C Connection 12 LEAD ZIG-ZAG ...
Page 2
... Sustained short circuit current 300% of the rated current for up www.DataSheet4U.com to 10 seconds Self-Ventilated and Drip-Proof Superior Voltage Waveform Digital, Solid State, Volts-per-Hertz Regulator No Load to Full Load Regulation 2 200-JC6dt3 / / / / Complete Range of Accessories // Permanent Magnet Generator (PMG) - Optional // - Brushless, Rotating Field - 300% Short Circuit Capability ...
Page 3
... Cold Cranking Amps Under 0°F (-17.8°C) // Fuel System Fuel Supply Connection Size Fuel Return Connection Size Maximum Fuel Lift: ft (m) Recommended Fuel Total Fuel Flow: gal/hr (lit/hr) www.DataSheet4U.com 3 200-JC6dt3 / / / / Fuel Consumption // John Deere 6068HF485 At 100% of Power Rating: gal/hr (lit/hr) 4-Cycle At 75% of Power Rating: gal/hr( lit/hr) 6-Inline At 50% of Power Rating: gal/hr (lit/hr) 415 (6 ...
Page 4
... Fax +49 7541 90 7084 / powergenregion1@mtu-online.com Phone + 65 6861 5922 / Fax + 65 6861 3615 / powergenregion2@mtu-online.com 56001 / USA / Phone + 1 507 625 7973 / Fax + 1 507 625 2968 / powergenregion3@mtu-online.com Germany / Phone + 49 89 203042 800 / Fax +49 89 203042 900 / info@cfc-solutions.com //www.mtu-online.com 4 200-JC6dt3 / / / / Weight (less tank) 3,525 lb (1,599 kg) Standby Full Load ...