125-JC6DT3 MTU Onsite Energy, 125-JC6DT3 Datasheet

no-image

125-JC6DT3

Manufacturer Part Number
125-JC6DT3
Description
DIESEL ENGINE-GENERATOR SET
Manufacturer
MTU Onsite Energy
Datasheet
www.DataSheet4U.com
DIESEL ENGINE-GENERATOR SET
125-JC6DT3
125 ekW
115 ekW
208 - 600V
SySTEm RATINGS
Standby
Prime
Voltage (L-L)
Phase
PF
Hz
kW
kVA
AMPS
skVA@30%
Voltage Dip
Generator Model*
Temp Rise
Connection
Voltage (L-L)
Phase
PF
Hz
kW
kVA
AMPS
skVA@30%
Voltage Dip
Generator Model*
Temp Rise
Connection
* The Generator Model Number identified in the table is for standard C Series Configuration. Consult the factory for alternate configuration.
** UL2200 Offered
/
/
60 Hz
60 Hz
240V**
1
1.0
60
125
125
521
136
431PSL6204
130°C/27°C
12 LEAD ZIG-ZAG
240V
1
1.0
60
115
115
479
136
431PSL6204
105°C/40°C
12 LEAD ZIG-ZAG
/
/
Prime
Standby
240V**
1
1.0
60
125
125
521
195
431PSL6224
130°C/27°C
4 LEAD
240V
1
1.0
60
115
115
479
195
431PSL6224
105°C/40°C
4 LEAD
208V**
3
0.8
60
125
156.25
434
250
363CSL1607
130°C/27°C
12 LEAD LOW WYE
208V
3
0.8
60
115
138
399
250
363PSL1607
105°C/40°C
12 LEAD LOW WYE
240V**
3
0.8
60
125
156.25
376
250
363CSL1607
130°C/27°C
12 LEAD HI DELTA
240V
3
0.8
60
115
143.75
346
250
363PSL1607
105°C/40°C
12 LEAD HI DELTA
A tognum grouP BrAnd
480V**
3
0.8
60
125
156.25
188
330
363CSL1607
130°C/27°C
12 LEAD HI WYE
480V
3
0.8
60
115
143.75
173
330
363PSL1607
105°C/40°C
12 LEAD HI WYE
600V**
3
0.8
60
125
156.25
150
334
363PSL1658
125°C/40°C
4 LEAD WYE
600V
3
0.8
60
115
143.75
138
335
363PSL1658
105°C/40°C
4 LEAD WYE

Related parts for 125-JC6DT3

125-JC6DT3 Summary of contents

Page 1

... DIESEL ENGINE-GENERATOR SET 125-JC6DT3 125 ekW / Standby / / 115 ekW 60 Hz Prime 208 - 600V SySTEm RATINGS Standby Voltage (L-L) 240V** Phase 125 kVA 125 AMPS 521 skVA@30% Voltage Dip 136 Generator Model* 431PSL6204 Temp Rise 130°C/27°C Connection 12 LEAD ZIG-ZAG ...

Page 2

... Sustained short circuit current 300% of the rated current for seconds www.DataSheet4U.com Self-Ventilated and Drip-Proof Superior Voltage Waveform Digital, Solid State, Volts-per-Hertz Regulator No Load to Full Load Regulation 2 125-JC6dt3 / / / / Complete Range of Accessories // Permanent Magnet Generator (PMG) - Optional // - Brushless, Rotating Field - 300% Short Circuit Capability ...

Page 3

... Cold Cranking Amps Under 0°F (-17.8°C) // Fuel System Fuel Supply Connection Size Fuel Return Connection Size Maximum Fuel Lift: ft (m) Recommended Fuel Total Fuel Flow: gal/hr (lit/hr) www.DataSheet4U.com 3 125-JC6dt3 / / / / Fuel Consumption // John Deere 6068HF285 At 100% of Power Rating: gal/hr (lit/hr) 4-Cycle At 75% of Power Rating: gal/hr( lit/hr) 6 In-Line At 50% of Power Rating: gal/hr (lit/hr) 415 (6 ...

Page 4

... Fax +49 7541 90 7084 / powergenregion1@mtu-online.com Phone + 65 6861 5922 / Fax + 65 6861 3615 / powergenregion2@mtu-online.com 56001 / USA / Phone + 1 507 625 7973 / Fax + 1 507 625 2968 / powergenregion3@mtu-online.com Germany / Phone + 49 89 203042 800 / Fax +49 89 203042 900 / info@cfc-solutions.com //www.mtu-online.com 4 125-JC6dt3 / / / / Weight (less tank) 2,821 lb (1,280 kg) Standby Full Load Standby no Load 91 ...