200-240V Allen-Bradley, 200-240V Datasheet - Page 14

no-image

200-240V

Manufacturer Part Number
200-240V
Description
Adjustable Frequency Ac Drives
Manufacturer
Allen-Bradley
Datasheet
14
Input/Output Ratings
Output Frequency: 0-400 Hz (Programmable)
Efficiency: 97.5% (Typical)
Digital Control Inputs (Input Current = 6mA)
SRC (Source) Mode:
Control Output (Programmable Output, form C relay)
Resistive Rating: 3.0A at 30V DC, 125V AC and 240V AC
Recommended Fuses and Circuit Breakers
Fuse: UL Class J, RK1, T or Type BS88; 600V (550V) or equivalent. Circuit Breakers: HMCP or Bulletin 140M or equivalent.
Protective Features
Motor Protection: I 2 t overload protection - 150% for 60 Secs, 200% for 3 Secs (Provides Class 10 protection)
Overcurrent: 200% hardware limit, 300% instantaneous fault
Over Voltage:
Under Voltage:
Control Ride Through: Minimum ride through is 0.5 Secs - typical value 2 Secs
Faultless Power Ride Through: 100 milliseconds
Dynamic Braking
Internal brake IGBT included with power ratings 5.5 kW (7.5 HP) and 7.5 kW (10.0 HP) for 240V, 3-phase drives and 5.5 kW
(7.5 HP), 7.5 kW (10.0 HP) and 11.0 kW (15.0 HP) for 480V, 3-phase drives. See the PowerFlex 4M User Manual for ordering
information.
Category
Environment
Control
18-24V = ON
0-6V = OFF
100-120V AC Input – Trip occurs at 405V DC bus voltage (equivalent to 150V AC incoming line)
200-240V AC Input – Trip occurs at 405V DC bus voltage (equivalent to 290V AC incoming line)
380-460V AC Input – Trip occurs at 810V DC bus voltage (equivalent to 575V AC incoming line)
100-120V AC Input – Trip occurs at 210V DC bus voltage (equivalent to 75V AC incoming line)
200-240V AC Input – Trip occurs at 210V DC bus voltage (equivalent to 150V AC incoming line)
380-480V AC Input – Trip occurs at 390V DC bus voltage (equivalent to 275V AC incoming line)
Specification
Altitude:
Maximum Surrounding Air
Temperature without derating:
Cooling Method
Storage Temperature:
Atmosphere:
Relative Humidity:
Shock (operating):
Vibration (operating):
Carrier Frequency
Frequency Accuracy
Speed Regulation - Open Loop
with Slip Compensation:
Stop Modes:
Acceleration/Deceleration:
Intermittent Overload:
Electronic Motor Overload
Protection
IP20:
IP20 zero stacking:
Convection:
Fan:
Digital Input:
Analog Input:
SNK (Sink) Mode:
0-6V = ON
18-24V = OFF
Approvals
Analog Control Inputs
4-20mA Analog: 250 ohm input impedance
0-10V DC Analog: 100k ohm input impedance
External Pot: 1-10k ohms, 2 Watt minimum
Inductive Rating: 0.5A at 30V DC, 125V AC, and 240V AC
1000 m (3300 ft) max. without derating
–10 to 50° C (14 to 122° F)
–10 to 40° C (14 to 104° F)
120V, 1-Phase, 0.75 kW (1 HP) and below
240V, 1-Phase, 0.4 kW (0.5 HP) and below
240V, 3-Phase, 0.75 kW (1 HP) and below
480V, 3-Phase, 0.75 kW (1 HP) and below
All other drive ratings.
–40 to 85 degrees C (–40 to 185 degrees F)
Important: Drive must not be installed in an
area where the ambient atmosphere contains
volatile or corrosive gas, vapors or dust. If the
drive is not going to be installed for a period of
time, it must be stored in an area where it will not
be exposed to a corrosive atmosphere.
0 to 95% non-condensing
15G peak for 11ms duration (±1.0ms)
1G peak, 5 to 2000 Hz
2-10 kHz. Drive rating based on 4 kHz.
Within ±0.05% of set output frequency.
Within 0.5% of maximum output frequency.
±2% of base speed across a 40:1 speed range.
Multiple programmable stop modes including -
Ramp, Coast, DC-Brake, Ramp-to-Hold and
S Curve.
Two independently programmable acceleration
and deceleration times. Each time may be
programmed from 0 - 600 seconds in 0.1 second
increments.
150% Overload capability for up to 1 minute
200% Overload capability for up to 3 seconds
Class 10 protection with speed sensitive
response and power-down overload retention
function.
U L
®
D
UL508C
EMC Directive 89/336
LV:
EMC:
C
EN 50178, EN 60204
EN 61800-3, EN 50081-1, EN 50082-2
U L
®
D
CSA 22.2

Related parts for 200-240V