Table 2.1: Connections of the SC2-2 OSSD module
Terminal
10
11
12
13
14
15
16
1
2
3
4
5
6
7
8
9
Assignment
pnp output readiness for
startup message
PNP output OSSD reporting
OFF
PNP output OSSD reporting
ON
0 V internal
Startup enable for input (RI) Normally open contact for start/restart interlock. It should be wired in if no function is acti-
24 V internal
Relay monitor input (RM)
24 V internal
24 V DC
0 V
24 V internal
Test input
OSSD1.1
OSSD1.2
OSSD2.1
OSSD2.2
Function
Option for connecting external indicator lamps to indicate restart (start) or error message
(see section 3.1)
Option for connecting external indicator lamps to indicate the OSSD state Off
Option for connecting external indicator lamps to indicate the OSSD state On
Reference point for pnp outputs
vated (see section 3.1)
Relay monitor input. It should be wired in if no function is activated (see section 3.2)
Supply voltage connection, protected from reverse polarity
Normally open contact for testing or error enable
OSSD relay output 1 NO (normally open)
OSSD relay output 2 NO
Copyright Pepperl+Fuchs, Printed in Germany
The SC2-2 control unit