■ Ratings
Note: 1. DC power supply models require a control power supply capacity of approximately 1 A per Unit when power is turned ON. Particular attention is
Power supply voltage
Allowable power supply voltage range
Power consumption
(See note 1.)
Current consumption
Input
A/D conversion method
External power supply
Event inputs
(See note 2.)
Output ratings
(depends on the
model)
Display method
Main functions
Ambient operating temperature
Ambient operating humidity
Storage temperature
Altitude
Accessories
2. PNP input types are also available.
3. For K3HB-series DeviceNet models, use only the DeviceNet Connector included with the product. The crimp terminals provided are for Thin Ca-
required when using two or more DC power supply models. The OMRON S8VS-series DC Power Supply Unit is recommended.
bles.
Timing input
Startup compensa-
tion timer input
Hold input
Reset input
Bank input
Relay output
Transistor output
Linear output
100 to 240 VAC (50/60 Hz), 24 VAC/VDC, DeviceNet power supply: 24 VDC
85% to 110% of the rated power supply voltage, DeviceNet power supply: 11 to 25 VDC
100 to 240 V: 18 VA max. (max. load)
24 VAC/DC: 11 VA/7 W max. (max. load)
DeviceNet power supply: 50 mA max. (24 VDC)
Platinum-resistance thermometer: Pt100
Thermocouple: K, J, T, E, L, U, N, R, S, B, W
Delta-Sigma method
See Sensor Power Supply/Output Type Codes
NPN open collector or no-voltage contact signal
ON residual voltage: 3 V max.
ON current at 0 Ω: 17 mA max.
Max. applied voltage: 30 VDC max.
OFF leakage current: 1.5 mA max.
NPN open collector or no-voltage contact signal
ON residual voltage: 2 V max.
ON current at 0 Ω: 4 mA max.
Max. applied voltage: 30 VDC max.
OFF leakage current: 0.1 mA max.
250 VAC, 30 VDC, 5 A (resistive load)
Mechanical life expectancy: 5,000,000 operations, Electrical life expectancy: 100,000 operations
Maximum load voltage: 24 VDC, Maximum load current: 50 mA, Leakage current: 100 μA max.
Linear output 0 to 20 mA DC, 4 to 20 mA DC:
Linear output 0 to 5 VDC, 1 to 5 VDC, 0 to 10 VDC:
Negative LCD (backlit LED) display
7-segment digital display (Character height: PV: 14.2 mm (green/red); SV: 4.9 mm (green)
Temperature input shift, measurement operation selection, averaging, previous average value comparison,
zero-limit, output hysteresis, output OFF delay, output test, display value selection, display color selection, key
protection, bank selection, display refresh period, maximum/minimum hold, reset
−10 to 55°C (with no icing or condensation)
25% to 85%
−25 to 65°C (with no icing or condensation)
2,000 m max.
Watertight packing, 2 fixtures, terminal cover, unit stickers, instruction manual. DeviceNet models also include
a DeviceNet connector (Hirose HR31-5.08P-5SC(01)) and crimp terminals (Hirose HR31-SC-121) (See note
3.)
Load: 500 Ω max, Resolution: Approx. 10,000, Output error: ±0.5% FS
Load: 5 kΩ max, Resolution: Approx. 10,000, Output error: ±0.5% FS
(1 V or less: ±0.15 V; not output for 0 V or less)
K3HB-H