PCM50UD01 XPPOWER [XP Power Limited], PCM50UD01 Datasheet

no-image

PCM50UD01

Manufacturer Part Number
PCM50UD01
Description
AC-DC Power Supplies
Manufacturer
XPPOWER [XP Power Limited]
Datasheet
50/80/120 Watts
PCM Series
Specification
Output
Input
Input Voltage
Input Frequency
Input Current
Inrush Current
Power Factor
Earth Leakage Current • 180 µA max at 132 VAC/60Hz
Output Voltage
Minimum Load
Start Up Delay
Hold Up Time
Line Regulation
Load Regulation
Transient Response
Ripple & Noise
Overvoltage Protection • 112-132% with auto recovery on V1
Overcurrent Protection • 110-200% with auto recovery
Temperature
Coefficient
• 90-264 VAC
• 47-63 Hz
• PCM50:
• 30 A at 115 VAC or
• PCM50: 0.55 typical
• See tables
• No minimum load required for single
• 2 s max
• 10 ms min at low line
• ±1% max at full load for ±10% change
• ±5% max
• 5% max. deviation, 500 µs recovery time
• 2% pk-pk, 20MHz BW
• ±0.05% /˚C
PCM80:
PCM120:
60 A at 230 VAC at 25 ˚C cold start
PCM80/120: 0.94 min
300 µA max at 264 VAC/50Hz
output models. See tables for multi
output models
in input
for a 50% load change
on all outputs
1.35 A max
1.30 A max
1.60 A max
General
Environmental
EMC & Safety
Efficiency
Isolation
Switching Frequency
MTBF
Operating Temperature • PCM50: 0 ˚C to +70 ˚C, derate from 100%
Storage Temperature
Emissions
Harmonic Currents
Voltage Flicker
ESD Immunity
Radiated Immunity
EFT/Burst
Surge
Conducted Immunity
Power Frequency
Magnetic Fields
Dips & Interruptions
Safety Approvals
4000 VAC Isloation
Low Leakage Current
Single, Dual and Triple Outputs
Worldwide Medical Approvals
CCC Approved (PCM80)
Both Line and Neutral Fused
Non-standard Connectors Available
• Single output models: 80% typical
• 4000 VAC Input to Output
• PCM50: 64 kHz typical
• 100 kHrs at full load and 25 ˚C ambient
• PCM50/80: -40 ˚C to +80 ˚C
• EN55022, level B conducted
• EN61000-3-2, class A
• EN61000-3-3 amendments 1 & 2
• IEC61000-4-2, level 3
• IEC61000-4-3 10 V/m, level 3
• IEC61000-4-4, level 3
• IEC61000-4-5, level 3
• IEC61000-4-6 10 V/m, level 3
• IEC61000-4-8 10 A/m, Perf Criteria B
• IEC61000-4-11, 30% 500 ms,
• UL60601-1, CSA C22.2 No. 601.1 per cUL
Multi output models: 75% typical
1500 VAC Input to Ground
500 VAC Output to Ground
PCM80: 55 kHz typical
PCM120: 120 kHz typical
per MIL-HDBK-217F
load at 50 ˚C to 50% load at +70 ˚C
PCM80: 0 ˚C to +70 ˚C, derate from 100%
load at 40 ˚C to 50% load at +70 ˚C
PCM120: 0 ˚C to +60 ˚C, derate from
100% load at 40 ˚C to 50% load at +60 ˚C
PCM120: -20 ˚C to +85 ˚C
EN55022, level B radiated
Perf Criteria B
Perf Criteria B
Perf Criteria B
Perf Criteria B
Perf Criteria B
60% 100 ms, 100 % 5000 ms
Perf Criteria A, A, C
EN60601-1, CCC (PCM80)
xppower.com

Related parts for PCM50UD01

PCM50UD01 Summary of contents

Page 1

Watts PCM Series Specification Input Input Voltage • 90-264 VAC Input Frequency • 47-63 Hz Input Current • PCM50: 1.35 A max PCM80: 1.30 A max PCM120: 1.60 A max Inrush Current • 115 VAC or ...

Page 2

... PCM50US18†* 2% PCM50US24†* 2% PCM50US28†* 2% PCM50US36† 2% PCM50US48†* Output 3 Model Number Vnom Imin Imax Tol. (1) PCM50UD00† PCM50UD01 PCM50UD02† PCM50UD03 PCM50UD04 PCM50UD05 PCM50UD06† PCM50UD07† PCM50UD08† PCM50UD10 PCM50UD11 -5.0 V 0 PCM50UT01† -12.0 V 0 PCM50UT02† ...

Page 3

Models and Ratings Output 1 Output Power Vnom Imin Imax Tol. 50.0 W 3.3 V 0 65.0 W 5.0 V 0 70.0 W 7.0 V 0 75.0 W ...

Page 4

Models and Ratings Maximum Output Voltage Output Power 108 W 113 W 120 W 120 W 120 W Notes 1. Peak current is 5 seconds maximum duration with a 10% duty cycle. † Available from Farnell InOne. See pages 236-237 ...

Related keywords