MSR10RD ALLEN-BRADLEY [Allen-Bradley], MSR10RD Datasheet

no-image

MSR10RD

Manufacturer Part Number
MSR10RD
Description
Tongue Interlocks
Manufacturer
ALLEN-BRADLEY [Allen-Bradley]
Datasheet
Safeguarding Applications
Tongue Interlocks
Trojan 5, MSR10RD, Bulletin 100, PLC, Dual Channel
Circuit Status
Circuit shown with guard door closed, ready for motor starting (via signals from the PLC).
Operating Principle
The Minotaur MSR10RD immediate action outputs at 13-14 are connected to inputs at the PLC and the delayed outputs at D13-D14 are
connected to the contactor K1. The relevant PLC outputs are connected to contactor K2. If the guard is opened the Minotaur contacts 13-14
immediately signal the PLC to stop the motor. The PLC then has a pre-set time limit (adjustable at the MSR10RD) to execute its shut down
sequence and switch OFF contactor K2. After this time period has elapsed, the delayed action outputs D13-D14 will switch off contactor K1,
thus ensuring isolation even if there is a hardware, program or systematic fault in the PLC.
Fault Detection
If either contactor K1or K2 sticks ON, the motor will stop on command but the Minotaur cannot be reset (thus the fault is revealed to the
operator).
A single fault detected on the Minotaur input and output circuits will result in the lock-out of the system to a safe state (OFF).
All safety critical single faults will be detected at the next opening of the guard.
Comment
This system has the high integrity of hard wiring and allows a correctly sequenced shut-down which protects the machine and program.
18-10
Guard
Closed
24V DC
Ground
11
12 22
21
33
34
Trojan
Interlock
Switch
MSR10RD
Minotaur
A1
A2
+
S13
S14
S23
S24 X2 14 24
X1
13
23
33
34
43
44 54 64
53 63
73 83 91
74 84 92
D14
D13
K1
D22
D21
Outputs
D13-D14
&
D21-D22
Are
Delayed
Action
Outputs
Inputs
PLC
K2
Bulletin 100S
or 700S
Momentary
Push
Button
Reset
L1 L2 L3
M
K1
K2
Contact
Protection
e.g. Thermal
Cut Out

Related parts for MSR10RD

Related keywords