FC-6324 GAMEWELL-FCI [Gamewell-FCI by Honeywell], FC-6324 Datasheet

no-image

FC-6324

Manufacturer Part Number
FC-6324
Description
SIX ZONE PANEL
Manufacturer
GAMEWELL-FCI [Gamewell-FCI by Honeywell]
Datasheet
tile, six-zone control with space for an optional digital com-
municator. It meets the requirements of NFPA Standard 72
for Central Station, Protected Premises, and Remote
(DACT) Supervising Station Fire Alarm Systems. It is Listed
to UL Standard 864, inherently power limited and meets all
UL transient immunity requirements.
effective approach to systems design, and allow a great de-
gree of flexibility in one enclosure. These features include
six (6) Class B, Style B initiating circuits and three (3) Class
B, Style Y notification appliance circuits rated up to 2.5 amps
each with a system maximum of 2.5 amperes. Notification
appliance circuits can be configured as silenceable or
non-silenceable.
the need for computers and associated software.
waterflow switches.
dow offering a view of LEDs displaying the status of vital
functions and allowing access to switches controlling system
operation. The surface mounted enclosure, with its slim ap-
pearance (3 3/8-inch depth) is designed to blend with any en-
vironment. Space is available for two (2) B-7R batteries.
tional switches and standby batteries is provided.
of selectable transmission formats to communicate to most
central stations. Other features of the communicator are: A
line-active indicator for each of two phone lines, “Kiss-Off”
signal LED, dual “low telephone voltage detect” circuitry,
and programmable event codes per format. The FC-6324
control is programmable for AC power loss delay required
for DACT operation.
tion to as many as four (4) Model FC-2866 remote annuncia-
tors.
which provides 34 predefined open collector outputs that can
be used to drive LEDs or relays.
The FC-6324 Fire Alarm Control panel is a proven, versa-
The many features of the FC-6324 control provide a cost
DIP switch programming is used throughout, eliminating
A time delay of 30, 60, or 90 seconds is available for
The control is housed in a red steel enclosure with a win-
Supervision of vital components, plug-in modules, func-
The optional digital communicator includes a wide range
A serial annunciator driver allows remote alarm annuncia-
Other optional modules include the FC-2880 I/O module
struments, Inc. for their use. Specifications subject to change without notice.
Specifications are provided for information only, are not intended to be used for installation purposes, and are believed to be accurate. However, no responsibility is assumed by Fire Control In-
16 Southwest Park, Westwood, MA 02090 USA TEL: (781) 471-3000 FAX: (781) 471-3099
UL
CSFM
AGENCY APPROVALS
DESCRIPTION
S1869
Approved
An ISO 9001 Certified Company
CONVENTIONAL FIRE ALARM CONTROL
Inherently Power Limited
DIP Switch Programming
Choice of Output Patterns Including
ANSI S3.41
Programmable Time Delay for
Waterflow Switches
Periodic Trouble Reminder
Walk Test Feature
Optional Digital Communicator with
Multiple Reporting Formats
Serial Annunciator Output
Surface Mount Technology
SIX ZONE PANEL
FC-6324
FEATURES
© 2000 All Rights Reserved
9020-0485/Ver. 1.6

Related parts for FC-6324

FC-6324 Summary of contents

Page 1

... DESCRIPTION The FC-6324 Fire Alarm Control panel is a proven, versa- tile, six-zone control with space for an optional digital com- municator. It meets the requirements of NFPA Standard 72 for Central Station, Protected Premises, and Remote (DACT) Supervising Station Fire Alarm Systems Listed to UL Standard 864, inherently power limited and meets all UL transient immunity requirements ...

Page 2

... FC-2880 151-00004 FC-2866 151-00005 FC-2104 151-00019 2190 151-00017 5230 151-00018 7860 151-00020 151-00009 FC-6324 PC FC-7628 151-00011 151-00012 FC-2104 DACT reporting formats are: SIA 3/1 1,400 or 2,300 Hz Contact ID SK 4/2 BFSK 1,400 or 2,300 Hz 9020-0485 FC-2866 Remote Zone Annunciator .090 amp. .295 amp. ...