Specifications of SU2200XLNAFTA

Power - Rated
2.2kVA / 1600W
Ac Outlets
7 (UPS)
Features
DB9 and USB Communications, Rack Mount
Backup Time - Max Load
4.5 minutes
Media Lines Protected
1 - RJ45 Line
Voltage - Output Per Connector
120V (6 NEMA 5-15/20R and 1 NEMA L5-20R)
Voltage - Input
120V / 20A
Cord Length
10' (3.05m)
Ac Input Connector
NEMA 5-20P
Connector - Ac Output
6 NEMA 5-15/20R and 1 NEMA L5-20R
Size
19.50" L x 9.00" W x 10.25" H (495.3mm x 228.6mm x 260.4mm)
Weight
53 lbs (24kg)
Ac Output Connector
6 NEMA 5-15/20R and 1 NEMA L5-20R
Lead Free Status / RoHS Status
Lead free / RoHS Compliant
Specifications
OUTPUT
Output Volt Amp
Capacity (VA)
Output kVA capacity
(kVA)
Output Watt Capacity
(watts)
Output kW capacity
Output power factor
Crest Factor
Nominal Output
Voltage(s) Supported
Nominal Voltage
details
Frequency
compatibility
Frequency
compatibility details
Output voltage
regulation (line mode)
Output voltage
regulation (Economy
line mode)
Output voltage
regulation (Battery
mode)
Built-in UPS output
receptacles
Corrects line voltage conditions as low as 65V and as high as 138V back to selectable 110/120V (+/-2%) values
Standard internal battery set offers 14 minutes runtime at half load (800W) and 4.5 minutes at full load (1600W)
Optional BP48V60-3UNAFTA external battery packs offer expandable battery runtime
Space saving upright tower format
Fault tolerant auto-bypass maintains continuous utility output to connected equipment, even in cases where the UPS suffers internal failure
and requires maintenance
Network interfaces support simultaneous communications via built-in USB, DB9 serial and SNMPWEBCARD slot
HID compliant USB interface enables integration with built-in power management and auto shutdown features of Windows and Mac OS X
Included PowerAlert UPS monitoring software supports safe unattended shutdown, monitoring and control via local connected servers, plus
any number of additional servers over IP
UPS interface supports on-battery, low-battery, power-restored, AC-voltage, DC-voltage, output current monitoring, battery charge current,
battery capacity, AC line frequency, timed inverter shutoff, activate self-test, load bank output power control and remote reboot, UPS
nominal voltage adjustment and UPS line to battery power voltage setpoints
Built-in Emergency Power Off (EPO) interface with cable
NEMA 5-20P input plug (user-installable NEMA 5-15P replacement plug included)/NEMA 5-15/20R & NEMA L5-20R output receptacles
Integrated 2 bank switched PDU enables remote outlet management for load shedding or remote reboot of individual load banks
Front panel LEDs offer current monitoring and battery charge level information
UPS ships fully assembled in full compliance with DOT regulations, no time consuming connection of internal batteries by user required
Single line TEL/DSL or network ethernet line surge suppression
2 year manufacturer's product warranty, $250,000
2200
2.2
1600
1.6
0.7
3:1
110V; 120V
120V default
50 / 60 Hz
Output frequency matches input nominal on startup, defaults to 60 Hz on cold-start
+/- 2%
+/- 10%
+/- 2%
6 5-15/20R outlet(s); 1 L5-20R outlet(s)