SU2200XLNAFTA Tripp Lite, SU2200XLNAFTA Datasheet - Page 5

UPS TRUEONLINE 2.2KVA 1600W 7OUT

SU2200XLNAFTA

Manufacturer Part Number
SU2200XLNAFTA
Description
UPS TRUEONLINE 2.2KVA 1600W 7OUT
Manufacturer
Tripp Lite
Series
Smart Online™r
Type
UPSr
Datasheet

Specifications of SU2200XLNAFTA

Power - Rated
2.2kVA / 1600W
Ac Outlets
7 (UPS)
Features
DB9 and USB Communications, Rack Mount
Backup Time - Max Load
4.5 minutes
Media Lines Protected
1 - RJ45 Line
Voltage - Output Per Connector
120V (6 NEMA 5-15/20R and 1 NEMA L5-20R)
Voltage - Input
120V / 20A
Cord Length
10' (3.05m)
Ac Input Connector
NEMA 5-20P
Connector - Ac Output
6 NEMA 5-15/20R and 1 NEMA L5-20R
Size
19.50" L x 9.00" W x 10.25" H (495.3mm x 228.6mm x 260.4mm)
Weight
53 lbs (24kg)
Ac Output Connector
6 NEMA 5-15/20R and 1 NEMA L5-20R
Lead Free Status / RoHS Status
Lead free / RoHS Compliant
Shipping weight (lbs)
Shipping weight (kg)
UPS housing material
Cooling method
ENVIRONMENTAL
Operating
Temperature Range
Storage Temperature
Range
Relative Humidity
AC mode BTU / hr.
(full load)
AC economy mode
BTU / hr. (full load)
Battery mode BTU / hr.
(full load)
AC economy mode
efficiency rating (100%
load)
Audible Noise
COMMUNICATIONS
Communications
interface
Network monitoring
port description
PowerAlert software
Communications cable
WatchDog
compatibility
LINE / BATTERY TRANSFER
Transfer time
Low voltage transfer
to battery power
(setpoint)
High voltage transfer
to battery power
(setpoint)
SPECIAL FEATURES
Cold Start (startup in
battery mode during a
power failure)
High availability UPS
features
Green & high
efficiency features
CERTIFICATIONS
58.6
26.6
Steel
Fan
+32 to +104 degrees Fahrenheit / 0 to +40 degrees Celsius
+5 to +122 degrees Fahrenheit / -15 to +50 degrees Celsius
0 to 95%, non-condensing
812.9
347.2
885.6
94%
< 45 dB at front side 1m
DB9 Serial; Contact closure; EPO (emergency power off); Slot for SNMP/Web interface
Supports detailed monitoring of UPS and site power conditions; DB9 port supports RS232 and contact closure
communications
Included
DB9 cabling included
Supports Watchdog application, OS and hard-reboot restart options for remote applications
No transfer time (0 ms.) in online, double-conversion mode
80V (100% load), 65V (
138
Cold-start operation supported
Automatic inverter bypass; Hot swappable batteries
High efficiency economy mode operation; Individually controllable load banks; Schedulable daily hours of economy
mode operation