S8T-BUS03 Omron, S8T-BUS03 Datasheet - Page 6

no-image

S8T-BUS03

Manufacturer Part Number
S8T-BUS03
Description
CONNECTOR DC LINE BUS
Manufacturer
Omron
Series
S8TSr
Datasheet

Specifications of S8T-BUS03

Accessory Type
Bus Line Connectors
For Use With/related Products
S8TS Power Supplies
Lead Free Status / RoHS Status
Lead free / RoHS Compliant
Other names
S8TBUS03
Backup Function
S8T-DCBU-01 detects output voltage drop of S8TS-06024@ to
switch to backup operation.
Backup operation continues for about 7 seconds even after the
output voltage of S8TS-06024@ is restored.
Note: (1) If this state occurs, the S8TS-06024@ may be overloaded or malfunctioning.
Charging Circuit
Charging Time (Reference Values)
Note: The battery takes the time specified above to be charged.
LED lit
(DC ON: Green)
LED lit
(BACKUP: Red)
Power failure
Failure
of one
unit of
S8TS-
06024@
Upon activation of
overload protection
function of S8TS-
06024@ (See note.)
LC-@122R2@@
LC-@123R4@@
Indicator
45
0
Battery used
(2) If switching between backup operation and normal operation is repeated,
(3) The contact capacity of the relay is 24 VDC 0.1 A.
(4) Do not use the S8TS-06024@ with sudden load fluctuations or load peaks
(5) The maximum inrush current specified below flows when backup operation
If power is interrupted for shorter than the necessary charging
time (i.e., power failure immediately after installation or
repeated short power failures), backup operation may not
continue for the necessary time.
Immediately eliminate the cause of the trouble.
the output voltage changes accordingly.
exceeding the rated current. Doing so will cause the output voltage of the
S8TS-06024@ to drop and backup to be performed, and may shorten the
battery service life.
starts.
During
operation
of one unit
of S8TS-
06024@
During
operation
of multiple
units of
S8TS-
06024@
25 ms
Operation mode
Relay (OPN MODE)
(1)-(2): ON
output relay
Backup
Normal
Time
COM
Continuous
backup
operation
Repetition of
switching
between
Normal
operation and
Backup
operation at an
interval of about
7 seconds
Backup status
24 to 48 hours
Battery charge status: Fully charged
Battery ambient temperature: 40°C
Input capacitor of connected equipment: 56,000 µF
Load power: 192 W
1
2
3
100% charged
Lit
Blink at an
interval of
about 7
seconds
(BACKUP:
Red)
LED
5 hours
8 hours
80% charged
Backup
(1)-(2): ON
Repetition of
switching
between Normal
((3)-(2): ON)
and BACK UP
((1)-(2): ON) at
an interval of
about
7 seconds.
(OPN MODE)
Relay
Output Voltage Adjustment for
S8TS-06024@
The DC Backup Block detects a drop in the output voltage (approx.
23 VDC) of the connected S8TS-06024@ to switch to backup
operation.
The output voltage of the S8TS-06024@ can be adjusted using the
output voltage adjuster. Do not, however, set the output voltage to
lower than the factory shipment setting, if the S8TS-06024@ is used
connected with a DC Backup Block.
Wiring Length between S8T-DCBU-01
and Battery
Connect S8T-DCBU-01 and the battery using a cable having a wire
diameter specified in Recommended Wire Diameter on page 16
within a wiring length of 1.5 m.
Because the battery voltage is monitored at the battery connecting
terminal, a large wiring impedance increases the voltage drop from
wiring, reducing the backup time.
Battery Holder S82Y-TS01
We recommend using the S82Y-TS01 Battery Holder for connecting
and installing the battery. Take the following points into consideration
when using the S82Y-TS01:
(1) Contact between leaking battery fluid and metal parts having an
(2) The inrush current shown below flows when backup operation is
(3) In the event that the battery generates inflammable gases, place
(4) If the S8T-DCBU-01 is stored with the AC power tuned OFF but
45
0
electric potential may cause ignition or fire. To prevent this, the
Battery Holder uses a resin battery tray. Install the Battery Holder
in the direction shown in the following figure.
switched to. The peak value and time of this inrush current vary
according to the capacity of the input capacitor of the connected
equipment, battery charge status, battery wiring length, and
ambient temperature. The switch and fuse of the S82Y-TS01 are
selected taking this inrush current into consideration. When
replacing the fuse, use only the specified fuse. (Littelfuse,
257015 (15 A))
the switch and fuse away from the convection path of the inflam-
mable gas to prevent the switch or fuse from causing ignition and
explosion.
the battery still connected, the standby current of the S8T-DCBU-
0 may cause the battery to discharge, considerably reduce the
service life of the battery, and render recharging and backup
impossible. To prevent this, turn OFF the switch. (Refer to Bat-
tery Overdischarge on page 4.)
25 ms
Time
Battery charge status: Fully charged
Battery ambient temperature: 40°C
Input capacitor of connected equipment: 56,000 µF
Load power: 192 W
S8T-DCBU-01
6