H3CA-A Omron, H3CA-A Datasheet - Page 3

RELAY TIMER SSR SPDT 24V

H3CA-A

Manufacturer Part Number
H3CA-A
Description
RELAY TIMER SSR SPDT 24V
Manufacturer
Omron
Series
H3CAr
Datasheet

Specifications of H3CA-A

Relay Type
Integrated
Function
Programmable (Multi-Function)
Circuit
SPDT (1 Form C)
Delay Time
0.1 Sec ~ 9990 Hrs
Output Type
Mechanical Relay
Contact Rating @ Voltage
3A @ 250VAC
Voltage - Supply
24 ~ 240VAC, 12 ~ 240VDC
Mounting Type
Socket
Termination Style
11 Pin Socketable
Timing Adjustment Method
Thumbwheel Switches
Timing Initiate Method
Input Voltage
Timing Range
0.1 s to 9990 Hrs
Supply Voltage
24 V to 240 V
Accuracy
+/- 0.3 %, - 0.05 s
Current Rating (max)
3 A
Display Type
LED Backlight
Operating Temperature Range
- 10 C to + 55 C
Output Current
3A
Supply Voltage Max
240VAC
Time Range Max
9990h
Switch Function
SPDT
Time Range Min
0.1s
No. Of Digits / Alpha
3
Supply Voltage Min
24VAC
Lead Free Status / RoHS Status
Lead free / RoHS Compliant
Lead Free Status / RoHS Status
Lead free / RoHS Compliant, Lead free / RoHS Compliant
Other names
H3CA-A
H3CAA
Z2359
Engineering Data
■ Life-test Curve
Nomenclature
LCD Display
Control output ON/OFF indication
Remaining time elapses, the
remaining time is indicated by a
pattern of bars in tenth of 1/10 of
the set time.
H3CA-A/H3CA-8H
Load current (A)
Operation Mode Selector (Fixed to "A" in H3CA-8H)
A: ON-delay operation
B: Flicker operation
C: Signal ON/OFF-delay operation (1)
D: Signal OFF-delay operation (1)
E: Interval operation
F: One-shot and flicker operation
G: Signal ON/OFF-delay operation (2)
H: Signal OFF-delay operation (2)
Time Unit Selector
Set Time Indicators (3 Digits)
Reference: A maximum current of 0.15 A can be switched at 125 VDC (cosφ = 1).
Note: 1. The H3CA Series has been tested for the following: impulse voltages, noise
2. Minimum applicable load (P reference values):
H3CA-A(FA), H3CA-8H: 100 mA at 5 VDC
H3CA-8: 10 mA at 5 VDC
(via noise simulator, for L loads, and for relay oscillation), and resistance to
static electricity.
Maximum current of 0.1 A can be switched if L/R is 7 ms. In both cases, a
life of 100,000 operations can be expected.
H3CA-FA
Operation Mode Selector
LCD Display
Set Time Indicators (3 Digits)
Time Unit Selector
H3CA
3

Related parts for H3CA-A