I800 Fluke Electronics, I800 Datasheet - Page 5

no-image

I800

Manufacturer Part Number
I800
Description
CURRENT CLAMP PROBE AC
Manufacturer
Fluke Electronics
Type
AC Clampr
Datasheet

Specifications of I800

Style
Pincer
Ac Current Range
100mA ~ 800A rms
Bandwidth
10kHz
Cable Length
62.992" (1600.00mm)
Max Conductor Size
2.126" (54.00mm)
Termination
Banana Plug, Double, Sheathed
Ratings
CAT III 600V
For Use With
614-1062 - DMM TRUE RMS 50000CNT W/BCKLGHT
Lead Free Status / RoHS Status
Lead free by exemption / RoHS compliant by exemption
Other names
2840283
The actual current in the conductor is 400 mA divided by 10-
turns, or 40 mA.
Maintenance
Performance Test
Verify Probe accuracy by measuring the output of a 20 A (±0.2
%), 60 Hz current source (Fluke 5100B and 5220A or
equivalent). When used with a compatible DMM with ± 0.75 % or
better ac current accuracy (Fluke 8060A or equivalent), the probe
should measure 20.00 A ± 0.40 A (20.00 mA, ± 0.40 mA). There
are no calibration adjustments in the Clamp.
Cleaning
Clean the case periodically by wiping it with a damp cloth and
detergent. Do not use abrasive cleaners or solvents. Do not
immerse the Clamp in liquids.
Specifications
Electrical Characteristics
Current Range
Continuous Measuring Range
Overload Capability
for 1 Hour, 33 % Duty Cycle
Output Sensitivity
Turns Ratio
Accuracy (at 100 A, 2 kHz, +25 °C) ± 1% of reading
Load Impedance
Phase Shift at 2 kHz
Frequency Range
Working Voltage
(see Safety Standards section)
General Characteristics
Maximum Conductor Size
Output Connection
Operating Temperature Range
Storage Temperature Range
Operating Humidity
800 A rms
100 mA to 800 A rms
1500 A rms (50/60 Hz)
1 mA / A
1000:1
≤ 20 Ω
± 1 degree
30 Hz to 10 kHz (-3 dB)
54 mm diameter
4 mm safety plugs
-10 to +55 °C
-40 to +70 °C
15 % to 85 %
(non condensing)
600 V ac rms or dc