1180-01-1A E-T-A, 1180-01-1A Datasheet

CIRCUIT BREAKER SP 1A

1180-01-1A

Manufacturer Part Number
1180-01-1A
Description
CIRCUIT BREAKER SP 1A
Manufacturer
E-T-A
Series
1180r
Datasheet

Specifications of 1180-01-1A

Breaker Type
Thermal
Voltage
72VDC, 250VAC
Current - Trip (it)
1A
Number Of Poles
1
Actuator Type
Push-Push
Mounting Type
Panel Mount
Lead Free Status / RoHS Status
Lead free / RoHS Compliant
Other names
1180-01-1AMP
302-1326
Miniaturised single pole thermal circuit breaker with switching function
optional (push-push actuation). Reliable snap-acting and trip-free
mechanism. Approved to CBE standard EN/IEC 60934. S-type, TO.
Blade terminals fitting into sockets for rail mounting.
Protection of loads in power distribution systems in control cabinets and
process control.
Type No.
1180
1180 - 01 - 1 A
Current
rating (A)
0.1
0.2
0.25
0.3
0.4
0.5
0.6
0.7
0.8
1
1.5
Authority
VDE
UL
CSA
Issue B
Description
Typical applications
Ordering information
Standard current ratings and typical internal resistance values
Approvals
single pole thermal circuit breaker, plug-in mounting
Versions
01
02
with switching function, without label
reset function only, without label
Current rating range
0.1...10 A
ordering example
Internal
resistance (Ω)
81
22
14
8.7
5.5
3.4
2.5
1.7
1.5
0.9
0.4
Voltage rating
AC 250 V; DC 65 V
AC 250 V; DC 72 V
AC 250 V; DC 72 V
Thermal Overcurrent Circuit Breaker 1180-...
Current
rating (A)
2
2.5
3
3.5
4
5
6
7
8
10
Current ratings
0.1...10 A
0.1...10 A
0.1...10 A
Internal
resistance (Ω)
0.25
0.18
0.11
0.08
0.07
≤ 0.05
≤ 0.05
≤ 0.05
≤ 0.05
≤ 0.05
www.e-t-a.com
Dielectric strength
(IEC 60664 and 60664A)
Humidity
Voltage rating
Current ratings
Typical life
Ambient temperature
Insulation co-ordination
(IEC 60664 and 60664 A)
Insulation resistance
Interrupting capacity I
Interrupting capacity
(UL 1077)
Degree of protection
(IEC 60529/DIN 40050)
Vibration
without terminal block
Shock
without terminal block
Corrosion
Mass
Technical data
operating area
installation area
cn
AC 250 V; DC 65 V
(UL, UL Canada: AC 250 V; DC 72 V)
0.1...10 A
6,000 operations at 1 x I
3,000 operations at 1 x I
500 operations at 2 x I
-20...+60 °C (T 60) -4...+140 °F
rated impulse
withstand voltage
2.5 kV
reinforced insulation in operating area
test voltage
AC 3,000 V
AC 1,500 V
> 100 MΩ (DC 500 V)
0.1...5 A 6 x I
6...10 A 8 x I
AC 250 V: 2,000 A
DC 65 V: 200 A
operating area IP40
terminal area IP00
5 g (57-500 Hz) ± 0.38 mm (10-57 Hz)
to IEC 60068-2-6, test Fc,
10 frequency cycles/axis and to EN 50155
25 g (11 ms)
to IEC 60068-2-27, test Ea
96 hours at 5 % salt mist,
to IEC 60068-2-11, test Ka
to IEC 60068-2-78, test Cab
approx. 15 g
240 hours at 95 % RH
1180-...
N
N
N
pollution
degree
2
N
N
(inductive)
(low-inductance)
(inductive)
1 - 41
1

Related parts for 1180-01-1A

1180-01-1A Summary of contents

Page 1

... Versions 01 with switching function, without label 02 reset function only, without label Current rating range 0.1...10 A 1180 - ordering example Standard current ratings and typical internal resistance values Current Internal Current rating (A) resistance (Ω) rating (A) ...

Page 2

... Thermal Overcurrent Circuit Breaker 1180-... Dimensions 24.4 .961 1 5.2 .205 14.5 .571 16.6 .654 18.2 .717 19,8 .780 slot for fitting labels (see accessory 1) Internal connection diagram Shock directions Typical time/current characteristics at +23 °C7+73.4 °F 1.1 .043 0.6 .024 3.1 .122 3 ...

Page 3

... Thermal Overcurrent Circuit Breaker 1180-... Accessories - Terminal block with screw terminals Label for circuit breaker 1180, surface for marking 4 (packaging quantity 120 pcs) Y 307 374 01 2 Terminal block for DIN rail mounting, with screw terminals conductor, width 8.2 mm, dimensions 64 x 42.5 x 8.2 mm, headroom over the upper rail edge with circuit breaker fitted (OFF position ...

Page 4

... Thermal Overcurrent Circuit Breaker 1180-... Accessories - Terminal block with spring-loaded terminals Label for circuit breaker 1180, surface for marking 4 (packaging quantity 120 pcs) Y 307 374 01 7 Terminal block for DIN rail mounting, with spring-loaded terminals conductor, width 8.2 mm, dimensions 68.5 x 36.5 x 8.2 mm, headroom over the upper rail edge with circuit breaker fitted (OFF position ...

Related keywords