ESX10-124-DC24V-10A E-T-A Circuit Protection and Control, ESX10-124-DC24V-10A Datasheet

no-image

ESX10-124-DC24V-10A

Manufacturer Part Number
ESX10-124-DC24V-10A
Description
CIRCUIT PROTECTOR; 10 A CLASS I, DIVISION 2 ; RESET INPUT AND STATUS OUTPUT ; 24
Manufacturer
E-T-A Circuit Protection and Control
Type
Electronicr
Datasheet

Specifications of ESX10-124-DC24V-10A

Actuator Type
Toggle
Brand/series
ESX10
Current, Rating
10 A
Mounting Type
Plug-In
Number Of Poles
1
Termination
Blade
Voltage, Rating
24 VDC
Lead Free Status / Rohs Status
RoHS Exempt Product
Electronic circuit protector type ESX10 is designed to ensure selective
disconnection of DC 24 V load systems.
DC 24 V power supplies, which are widely used in industry today, will
shut down the output in the event of an overload with the result that
one faulty load in the system can lead to complete disconnection of
all loads. As well as an unidentified failure this also means stoppage
of the whole system.
Through selective disconnection the ESX10 responds much faster
to overload or short circuit conditions than the switch-mode power
supply. This is achieved by active current limitation. The ESX10 limits
the highest possible current to values between 1.3 to 1.8 times the
selected rated current of the circuit protector. Thus it is possible to
switch on capacitive loads of up to 20,000 μF lamp loads, but they
are disconnected only in the event of an overload or short circuit.
For optimal alignment with the characteristics of the application the
current rating of the ESX10 can be selected in fixed values from
0.5 A...12 A. Failure and status indication are provided by a multicolour
LED and an integral short-circuit-proof status output or a potential-free
signal contact.
The ESX10, with a width of only 12.5 mm, can be plugged into the
E-T-A power distribution socket Module 17plus ensuring ease of
installation and saving space in control cabinets.
Upon detection of overload or short circuit in the load circuit, the
MOSFET of the load output will be blocked to interrupt the
current flow. The MOSFET and the load circuit may be re-activated
via the remote electronic reset input or manually by means of the
ON/OFF button. When starting up the system, the load circuit may
also be manually disconnected.
Authority
UL 2367
UL 508
CSA C22.2 No: 14
Issue C
Attention:
Description
Features
Approvals
The user should ensure that the cable cross sections of the relevant
load circuit are suitable for the current rating of the ESX10 used.
Automatic start-up of machinery after shut down must be prevented
(Machinery Directive 98/37/EG and EN 60204-1). In the event of
a short circuit or overload the load circuit will be disconnected
electronically by the ESX10.
Selective load protection, electronic trip characteristics.
Active current limitation for safe connection of capacitive loads
up to 20,000 μF and on overload/short circuit.
Current ratings 0.5 A...12 A.
Reliable overload disconnection with 1.1 x I
load lines or small cable cross sections (see table 3).
Manual ON/OFF button (S1).
Control input IN+ for remote ON/OFF signal (option).
Clear status and failure indication through LED, status output SF
or Si contact F.
Electronic reset input RE (option).
Integral fail-safe element.
Width per unit only 12.5 mm.
Plug-in mounting utilising power distribution system Module 17plus
or SVSxx optionally (see product group Power distribution systems)
Electronic Circuit Protector ESX10
Voltage rating
DC 24 V
DC 24 V
DC 24 V
N
plus, even with long
Current ratings
0.5...12 A
0.5...12 A
0.5...12 A
www.e-t-a.com
Operating data
Operating voltage U
Current rating I
Closed current I
Status indication
by means of
Load circuit
Load output
Overload disconnection
Short-circuit current I
Trip time
Temperature disconnection internal temperature monitoring with
Low voltage monitoring
load output
Starting delay t
Disconnection of load circuit electronic disconnection
Free-wheeling circuit
Several load outputs must not be connected in parallel
for electronic disconnection typically 3 s at I
Technical data
N
start
0
S
GREEN:
ORANGE: in the event of overload or short circuit
RED:
OFF:
K
(T ambient = 25 °C, operating voltage U S = DC 24 V)
DC 24 V (18...32 V)
fixed current ratings: 0.5 A, 1 A, 2 A, 3 A,
4 A, 6 A, 8 A, 10 A, 12 A
ON condition: typically 20...30 mA
depending on signal output
Power-MOSFET switching output
(high side switch)
typically 1.1 x I
active current limitation (see table 1)
see time/current characteristics
typically 3 s...100 ms at I
(or 1.5 x I
electronic disconnection
with hysteresis, no reset necessary
load “OFF” at U
typically 0.5 sec after every switch-on
and after applying U
external free-wheeling diode
recommended with inductive load
ESX10
multicolour LED:
unit is ON, power-MOSFET
is switched on
- status output SF ON,
until electronic disconnection
- unit electronically disconnected
- load circuit/Power-MOSFET OFF
- manually switched off (S1 = OFF)
- undervoltage (U
- after switch-on till the end
status output SF (option)
potential-free signal contact F (option)
ON/OFF/ condition of switch S1
supplies + DC 24 V
or device is dead
of the delay period
N
/1.3 x I
N
Load
S
(1.05...1.35 x I
N
< 8 V
)
S
> 1.1 x I
S
< 8 V)
Load
N
> 1.8 x I
N
)
5 - 27
N
5

Related parts for ESX10-124-DC24V-10A

ESX10-124-DC24V-10A Summary of contents

Page 1

... A...12 A. Failure and status indication are provided by a multicolour LED and an integral short-circuit-proof status output or a potential-free signal contact. The ESX10, with a width of only 12.5 mm, can be plugged into the E-T-A power distribution socket Module 17plus ensuring ease of installation and saving space in control cabinets. ...

Page 2

... A 120 mV 1 150 mV 1 180 mV 1 Attention: when mounted side-by-side without convection the ESX10-0.. should not carry more than its rated load with 100 % ON duty due to thermal effects Technical data Reset input RE Electrical data to terminal 12 of module 17plus S Reset signal RE ...

Page 3

... Please note: ● The user should ensure that the cable cross sections of the relvant load circuit are suitable for the current rating of the ESX10 used. ● Automatic start-up of machinery after shut down must be preven- ted (Machinery Directive 98/37/EG and EN 60204-1). In the event of a short circuit or overload the load circuit will be disconnected electronically by the ESX10 ...

Page 4

... Electronic Circuit Protector ESX10 ESX10 signal inputs / outputs (wiring diagrams) Signal contacts are shown in the OFF or fault condition. ESX10-100 without signal input/output ESX10-103 without signal input with signal output F (group signal, change-over) operating condition: SC/SO closed, SC-SI open fault condition: SC/SO open, SC-SI closed ...

Page 5

... Ohm = ( 0.050 max S ab The ESX10 reliably trips from 0 Ohm to max. circuitry resistance R Cable cross section cable length L in meter (= single length) Example 1: max. length at 1.5 mm Example 2: max. length at 1.5 mm Example 3: mixed wiring: (Control cabinet – sensor/actuator level 0.95 Ohm 0.71 Ohm Issue C ● ...

Page 6

... Electronic Circuit Protector ESX10 Dimensions 60 2.36 6x6.8=40.8 6x.267=1.60 50 1.97 This is a metric design and millimeter dimensions take precedence ( 5 All dimensions without tolerances are for reference only. In the interest of improved design, performance and cost effectiveness the right to make changes in these specifications without notice is reserved ...

Page 7

... The integral status output SF of the ESX10-104/-106/-124/-127 can be tapped at terminal 12 of the relevant channel (single signalisation). The reset input RE may be connected via terminal (ESX10- 124/-127) or terminal 12 (ESX10-125). The integral control input IN+ of ESX10-115 is connected via terminal 12. ...

Page 8

... Clip modules onto DIN rails. 2 Push modules together (side-by-side). left-side terminal block 3 Snap on right-side and left-side terminal blocks. 4 Cut busbar to required length and fit on supply side of the modules. 5 Connect line feed with spring-loaded terminals. 6 Plug in ESX10. inch 1 Line 1 Line Connection and disconnection of cables with screw driver www ...

Page 9

... LOAD 2 12 LOAD 2 LOAD 2 12 ESX10-104 left-side terminal block 11 GND 12 status indication SF +24V=OK 13, 14 looped through Issue C Connection diagram for ESX10-... Module 17plus with ESX10-101 LINE 1 LINE 1 busbar Supply 11 11 GND GND LOAD 2 12 LOAD 2 12 jumper right-side left-side terminal block ...

Page 10

... GND 12 status indication SF inverted, 0V=OK 13, 14 reset input RE (group reset), +24V falling edge *Caution: unused slots have to be fitted with jumpers Accessories: Module 17plus Connection diagram for ESX10-... Module 17plus with ESX10-115 module 2 LINE 1 LINE 1 busbar Supply 11 11 GND GND >i > ...

Page 11

... This is a metric design and millimeter dimensions take precedence ( mm ) Issue C Accessories for ESX10 Retaining clip Y 307 754 01 18.5 .728 2 .079 Mounting of retaining clip ESX10 with retaining clip Y 307 754 01 for power distribution system module 17plus top view 12.3 .484 Removal of retaining clip Y 307 754 01 inch www.e-t-a.com 5 ...

Page 12

... Pin selection, fitted with ESX10-124 (Example) female connector M4 Cu rail, tin-plated pressure-relief joint (1.1 mm (.043 in.) thick constriction) This is a metric design and millimeter dimensions take precedence ( Table 4: ESX10-... - Pin assignment 17-P10-Si -102 -103 -104 -105 LINE (+) LINE (+) LINE (+) LINE (+) DC +24 V ...