WDR-240-24 Mean Well, WDR-240-24 Datasheet

Linear & Switching Power Supplies 240W 24V 10A 180-550VAC

WDR-240-24

Manufacturer Part Number
WDR-240-24
Description
Linear & Switching Power Supplies 240W 24V 10A 180-550VAC
Manufacturer
Mean Well
Datasheet

Specifications of WDR-240-24

Product
Linear
Output Power Rating
240 W
Input Voltage
180 VAC to 550 VAC
Output Voltage (channel 1)
24 V
Output Current (channel 1)
10 A
Mounting Style
DIN Rail
Dimensions
125 mm L x 113.5 mm W x 35 mm H
Lead Free Status / RoHS Status
Lead free / RoHS Compliant
SPECIFICATION
MODEL
OUTPUT
INPUT
PROTECTION
FUNCTION
ENVIRONMENT
SAFETY &
EMC
(Note 4)
OTHERS
NOTE
AC CURRENT (Typ.)
INRUSH CURRENT (Typ.)
LEAKAGE CURRENT
OVERLOAD
OVER VOLTAGE
OVER TEMPERATURE
DC OK REALY CONTACT RATINGS (max.)
WORKING TEMP.
WORKING HUMIDITY
STORAGE TEMP., HUMIDITY
TEMP. COEFFICIENT
VIBRATION
SAFETY STANDARDS
WITHSTAND VOLTAGE
ISOLATION RESISTANCE
HARMONIC CURRENT
EMS IMMUNITY
MTBF
DIMENSION
PACKING
DC VOLTAGE
RATED CURRENT
CURRENT RANGE
RATED POWER
RIPPLE & NOISE (max.)
VOLTAGE ADJ. RANGE
VOLTAGE TOLERANCE
LINE REGULATION
LOAD REGULATION
SETUP, RISE TIME
HOLD UP TIME (Typ.)
VOLTAGE RANGE
FREQUENCY RANGE
EFFICIENCY (Typ.)
EMI CONDUCTION & RADIATION
240W Single Output Industrial DIN RAIL Power Supply
Note.6
Note.3
Note.5
Note.2
WDR-240-24
800ms, 150ms/400VAC
18ms / 400VAC
180 ~ 550VAC
47 ~ 63Hz
90
Protection type : Shut down o/p voltage, recovers automatically after temperature goes down
24V
10A
0 ~ 10A
240W
150mVp-p
24 ~ 28V
105 ~ 130% rated output power
29 ~ 33V
Protection type : Shut down o/p voltage, auto-recovery after 1 minute if the fault condition is removed
60Vdc/0.3A, 30Vdc/1A, 30Vac/0.5A resistive load
-30 ~ +70
20 ~ 95% RH non-condensing
-40 ~ +85 , 10 ~ 95% RH
Component:10 ~ 500Hz, 2G 10min./1cycle, 60min. each along X, Y, Z axes; Mounting: Compliance to IEC60068-2-6
UL508 approved, IEC60950-1 CB approved by SIQ, design refer to GL
I/P-O/P:3KVAC
I/P-O/P, I/P-FG, O/P-FG:>100M Ohms / 500VDC / 25 / 70% RH
Compliance to EN55022 (CISPR22), EN61204-3 Class B
Compliance to EN61000-3-2,-3
Compliance to EN61000-4-2,3,4,5,6,8,11, ENV50204, EN55024, EN61000-6-2 (EN50082-2), EN61204-3, heavy industry level, criteria A approved
141.1Khrs min.
63*125.2*113.5mm (W*H*D)
1.06Kg; 12pcs/13.7Kg/1.06CUFT
91%
1A/400VAC
COLD STAR 50A
<3.5mA / 530VAC
Protection type : Constant current limiting, unit will shut down after 3 sec. , auto-recovery after 1 minute if the fault condition is removed
1.0%
0.5%
1.0%
0.03%/
5
(TSW) detect on heatsink of power switch
(0 ~ 50
(Refer to output load derating curve)
2A/230VAC
I/P-FG:1.5KVAC
MIL-HDBK-217F (25 )
254 ~ 780VDC
18ms / 230VAC
1500ms, 150ms/230VAC at full load
at full load
O/P-FG:0.5KVAC
O/P-DC OK:0.5KVAC
WDR-240-48
48V
5A
0 ~ 5A
240W
150mVp-p
48 ~ 55V
56 ~ 65V
1.0%
0.5%
1.0%
WDR-240
File Name:WDR-240-SPEC 2010-11-09
series

Related parts for WDR-240-24

WDR-240-24 Summary of contents

Page 1

... Single Output Industrial DIN RAIL Power Supply SPECIFICATION MODEL WDR-240-24 DC VOLTAGE 24V RATED CURRENT 10A CURRENT RANGE 0 ~ 10A RATED POWER 240W RIPPLE & NOISE (max.) 150mVp-p Note.2 OUTPUT VOLTAGE ADJ. RANGE 24 ~ 28V VOLTAGE TOLERANCE Note.3 LINE REGULATION LOAD REGULATION SETUP, RISE TIME 800ms, 150ms/400VAC HOLD UP TIME (Typ ...

Page 2

... PWM & PFC CONTROL WDR-240 Case No. 979B TB2 Terminal Pin No. Assignment (TB1) Pin No. Assignment AC/L2 3 AC/L1 Terminal Pin No. Assignment (TB2) Pin No. Assignment 1,2 Relay Contact 3,4 DC OUTPUT +V 5,6 DC OUTPUT -V RECTIFIERS & FILTER O.C.P. DETECTION CIRCUIT O.V.P. File Name:WDR-240-SPEC 2010-11-09 series Unit: ...

Page 3

... Single Output Industrial DIN RAIL Power Supply Derating Curve 100 - AMBIENT TEMPERATURE ( ) Output derating VS input voltage 100 (VERTICAL) 180 WDR-240 200 300 400 450 500 INPUT VOLTAGE (V) 60Hz File Name:WDR-240-SPEC 2010-11-09 series 550 ...

Related keywords