NPS24-M Emerson Network Power, NPS24-M Datasheet
NPS24-M
Specifications of NPS24-M
Related parts for NPS24-M
NPS24-M Summary of contents
Page 1
NPS20-M Series 40 Watts Total Power Watts Input Voltage 264 VAC 127 - 300 VDC # of Outputs: Single Special Features • Medical and ITE Safety Approvals • Universal input • Less than 1U high • 2” x 4” footprint • Remote sense • Overload and short circuit protection • Adjustable output voltage • High efficiency • High MTBF • Built in EMI filter (CISPR 22 Class B) • International Efficiency Level V, Energy Star 2.0 & CeC compliant (NPS22-M < 38 Watt output) • Less than 300 mW no-load power consumption • 0˚C to +80˚C operation • Input power < 49 watts • Complies with EN61000 ...
Page 2
Environmental Specifications 0° °C ambient derate each output at 2.5% per degree from 50° °C. -20 °C start up Operating temperature: Storage temperature: -45 °C to +85 °C Electromagnetic susceptibility: Designed to meet EN61000-4; -2, -3, -4, -5, -6, -8, -11 Level 3 Humidity: Operating; non-condensing 10% to 90% RH Vibration: IEC68-2-6 to the levels of IEC721-3-2 MTBF demonstrated: > 550,000 hours at full load and 25 °C ambient conditions Mechanical Drawing M1 GND TAB (CN1) PIN 1 INPUT CONNECTOR (SK1) PIN 2 Ø (4.0) MOUNTING HOLE (4 PLACES) 0.197” (5.0) MINIMUM STANDOFF HEIGHT 4.00" (101.6) 3.73" (94.6) ...
Page 3
... Peak with 200LFM Regulation Load 1 Cooling Forced Air 2 1 0. NPS24-M NPS25-M Line Line Neutral Neutral +15 V +24 V +15 V +24 V Common Common Common Common -Sense -Sense +Sense +Sense Embedded Power for Business-Critical Continuity Americas 5810 Van Allen Way Ripple P/P ...