G2ZM20 TELE, G2ZM20 Datasheet - Page 2

no-image

G2ZM20

Manufacturer Part Number
G2ZM20
Description
MULTIFUNCTION(7 FT.)
Manufacturer
TELE
Datasheet

Specifications of G2ZM20

Contact Configuration
DPCO
Nom Input Voltage
240V
Delay Time Range
50ms To 100h
Adjustment Type
Screwdriver Slot
Relay Mounting
DIN Rail
Svhc
No SVHC (18-Jun-2010)
Contact Current Ac Max
5A
Contact
RoHS Compliant
Functions
ON delay (E)
When the supply voltage U is applied, the set interval t begins (green
LED U/t flashes). After the interval t has expired (green LED U/t
illuminated) the output relay R switches into on-position (yellow LED
illuminated). This status remains until the supply voltage is interrupted.
If the supply voltage is interrupted before the expiry of the interval t,
the interval already expired is erased and is restarted when the supply
voltage is next applied.
OFF delay (R)
The supply voltage U must be constantly applied to the device (green
LED U/t illuminated). When the control contact S is closed, the output
relay R switches into on-position (yellow LED illuminated). If the control
contact is opened, the set interval t begins (green LED U/t flashes).
After the interval t has expired (green LED U/t illuminated) the output
relay switches into off-position (yellow LED not illuminated). If the control
contact is closed again before the interval t has expired, the interval
already expired is erased and is restarted.
Single shot leading edge with control input (Ws)
The supply voltage U must be constantly applied to the device (green
LED U/t illuminated). When the control contact S is closed, the output
relay R switches into on-position (green LED U/t illuminated) and the set
interval t begins (green LED U/t flashes). After the interval t has expired
(green LED U/t illuminated) the output relay switches into off-position
(yellow LED not illuminated). During the interval, the control contact can
be operated any number of times. A further cycle can only be started
when the cycle run has been completed.
Single shot trailling edge with control input (Wa)
The supply voltage U must be constantly applied to the device (green
LED U/t illuminated). Closing the control contact S has no influence
on the condition of the output R. When the control contact is opened,
the output relay switches into on-position (yellow LED illuminated)
and the set interval t begins (green LED U/t flashes). After the interval
t has expired (green LED U/t illuminated), the ouput relay switches into
off-position (yellow LED not illuminated). During the interval, the control
contact can be operated any number of times. A further cycle can only
be started when the cycle run has been completed.
LED
LED
LED
LED
U/t
U/t
U/t
U/t
U
R
U
R
U
R
S
S
U
R
S
t
t
t
t
<t
<t
<t
t
t
www.tele-online.com
ON delay with control input (Es)
The supply voltage U must be constantly applied to the device (green
LED U/t illuminated). When teh control contact S is closed, the set
interval t begins (green LED U/t flashes). After the interval t has expired
(green LED U/t illuminated) the output relay R switches into on-position
(yellow LED illuminated). This status remains until the control contact is
opened again. If the control contact is opened before the interval t has
expired , the interval already expired is erased and is restarted with the
next cycle.
Single shot leading edge voltage controlled (Wu)
When the supply voltage U is applied, the output relay R switches
into on-position (yellow LED illuminated) and the set interval t begins
(green LED U/t flashes). After the interval t has expired (green LED U/t
illuminated) the output relay switches into off-position (yellow LED not
illuminated). This status remains until the supply voltage is interrupted.
If the supply voltage is interruted before the interval t has expired, the
output relay switches into off-position. The interval already is erased and
is restarted when the supply voltage is next applied.
Flasher pause first (Bp)
When the supply voltage U is applied, the set interval t begins (green
LED U/t flashes). After the interval t has expired, the output relay R
switches into on-position (yellow LED illuminated) and the set interval t
begins again. After the interval t has expired, the output relay switches
into off-position (yellow LED not illuminated). The output relay is
triggered at a ratio of 1:1 until the supply voltage is interrupted.
Flasher pulse first (Bi)
When the supply voltag U is applied, the output relay R switches
into on-position (yellow LED illuminated) and the set interval t begins
(green LED U/t flashes). After the interval t has expired, the output
relay R switches into off-position (yellow LED not illuminated) and the
set interval t begins again (green LED U/t flashes). The output relay is
triggered at a ratio of 1:1 until the supply voltage is interrupted.
LED
LED
LED
LED
U/t
U/t
U/t
U/t
U
R
U
R
U
R
U
R
S
t
t1
t
t
t
t
t
t
t
t
<t
<t
G2ZM20