TA11-A 100-230AC/DC IMO PRECISION CONTROLS, TA11-A 100-230AC/DC Datasheet

no-image

TA11-A 100-230AC/DC

Manufacturer Part Number
TA11-A 100-230AC/DC
Description
TIMER, MULTIFUNCTION, 100-230VAC/DC
Manufacturer
IMO PRECISION CONTROLS
Datasheet

Specifications of TA11-A 100-230AC/DC

Contact Configuration
DPDT
Nom Input Voltage
230V
Delay Time Range
0.05s To 60h
Adjustment Type
Knob
Relay Mounting
Plug-In
Svhc
No SVHC (15-Dec-2010)
Coil Voltage Vac Nom
230V
Contact
RoHS Compliant
New short-body on-delay, signal off-
delay, one shot or flicker (re-cycling)
timer modes, with 16 ranges, selectable
from the front panel
Timing ranges (selectable)
TA 1 1 - A
TA 1 1 - A
TA 1 1 - A
Calibrated range – selected
using screw in bottom left
corner of front panel
0-6
0-12
0-30
0-60
Repeat accuracy
Reset time
Max. switching frequency
Allowable ambient temperature
Mechanical life
Electrical life
Allowable operating voltage range
Contact ratings
Power consumption
Supply frequency AC types
Dielectric strength
Insulation resistance
Vibration
Shock
Options and ordering codes
Specifications
4 operation modes
Timing ranges 0.05 secs to 60 hours
16 ranges, front panel selectable
Indications for time range, operation
mode, time up and power on/timing
DPCO output relay
New scale ranges for ease of time setting
Instantaneous output with dial set at 0
Improved resistance to electromagnetic
interference
48-DIN
Plug-in 11-pin base
Sockets available for panel, surface or
DIN rail mounting
Approved by standards: UL and CSA
2 4 VA C / D C
1 0 0 - 2 4 0 VA C
4 8 - 1 2 7 V D C
Controlled timing range. Time unit selectable using the screw in the bottom right hand corner of the front panel
Time unit: 0.1 sec.
0.05-0.6 secs.
0.1-1.2
0.25-3
0.5-6
Electronic Multifunction Timer
±0.3% at max. setting time
0.1 sec or less
1800 times/hour
–10˚C to +55˚C (Avoid ice on timer)
20 million operations or more
100,000 operations or more at 250 V AC 5A resistive load
0.85 to 1.1 times input voltage (0.9 to 1.1 at 55˚C)
5A at 250 V AC resistive load
10VA at AC, 1W at DC
50/60 Hz
2,000 V AC rms. 1 min. between current carrying part and non current carrying part
2,000 V AC rms. 1 min. between output contacts and control circuit
1,000 V AC rms. 1 min. between open contacts
100 MΩ or more at 500 V DC megger
Mechanical durability: 10 to 55Hz, 0.75mm double amplitude
Mechanical durability: 10 to 55Hz, 0.5mm double amplitude
Mechanical durability: 500m/s
Malfunction durability: 100m/s
Time unit: sec.
0.5-6 secs.
1-12
2.5-30
5-60
2
2
(Approx. 50G)
(Approx. 10G)
Time unit: min.
0.5-6 mins.
1-12
2.5-30
5-60
Time unit: hrs.
0.5-6 hrs.
1-12
2.5-30
5-60
TA11-A
Guarantee
Year
3

Related parts for TA11-A 100-230AC/DC

TA11-A 100-230AC/DC Summary of contents

Page 1

... V AC rms. 1 min. between open contacts 100 MΩ or more at 500 V DC megger Mechanical durability 55Hz, 0.75mm double amplitude Mechanical durability 55Hz, 0.5mm double amplitude Mechanical durability: 500m/s 2 (Approx. 50G) Malfunction durability: 100m/s 2 (Approx. 10G) TA11-A 3 Year Guarantee Time unit: hrs. 0.5-6 hrs. 1-12 2.5-30 5-60 ...

Page 2

... Removing power while the timer is in operation or applying a reset signal resets the timer. Flush mounting Note: For flush mounting, an adaptor CTB is required (sold separately) Flush mounting – screw terminal STD-11 Net weight : Approx. 45g Flush mounting – solder terminal TA11 STF-11 ZSV11 ...

Page 3

... Further, repeated start signals within the elapsed time can prevent the output turning off indefinitely. Therefore, the TDMS can be used in conjunction with IMO sensors to detect that machine shafts have stopped rotating before maintenance is carried out. Contact IMO for details. Timer TA11-A 1. On-delay PO ...