ENYA series
7 Functions
7 time ranges
Wide input range
2 change over contacts
Width 35mm
Installation design
Technical data
1. Functions
The function has to be set before connecting the relay to the supply
voltage.
2. Time ranges
Time range Adjustment range
3. Indicators
Green LED U/t ON:
Green LED U/t flashes:
Yellow LED R ON/OFF: indication of relay output
4. Mechanical design
Self-extinguishing plastic housing, IP rating IP40
Mounted on DIN-rail TS 35 according to EN 60715
Mounting position: any
Shockproof terminal connection according to VBG 4 (PZ1 required),
IP rating IP20
Tightening torque: max. 1Nm
Terminal capacity:
5. Input circuit
Supply voltage:
Terminals:
Tolerance:
Rated consumption:
Rated frequency:
Duty cycle:
Reset time:
Residual ripple for DC:
Drop-out voltage:
Overvoltage category:
Rated surge voltage:
E
R
Ws
Wa
Es
Wu
Bp
1s
10s
1min
10min
1h
10h
100h
1 x 0.5 to 2.5mm² with/without multicore cable end
1 x 4mm² without multicore cable end
2 x 0.5 to 1.5mm² with/without multicore cable end
2 x 2.5mm² flexible without multicore cable end
Timers - Multifunction
ON delay
OFF delay
Single shot leading edge with control input
Single shot trailing edge with control input
ON delay with control input
Single shot leading edge voltage controlled
Flasher pause first
50ms
500ms
3s
30s
3min
30min
5h
1s
10s
1min
10min
1h
10h
100h
indication of supply voltage
indication of time period
12 to 240V AC/DC
A1(+)-A2
-10% to +10%
6VA (2W)
AC 48 to 63Hz
100%
100ms
10%
>30% of minimum rated supply voltage
III (in accordance with IEC 60664-1)
4kV
www.tele-online.com
6. Output circuit
2 potential free change over contacts
Rated voltage:
Switching capacity:
Fusing:
Mechanical life:
Electrical life:
Switching frequency:
Overvoltage category:
Rated surge voltage:
7. Control input
Input not potential free:
Loadable:
Max. line length:
Trigger level (sensitivity): automatic adaption to supply voltage
Min. control pulse length: DC 50ms / AC 100ms
8. Accuracy
Base accuracy:
Adjusting accuracy:
Repetition accuracy:
Voltage influence:
Temperature influence:
9. Ambient conditions
Ambient temperature:
Storage temperature:
Transport temperature:
Relative humidity:
Pollution degree:
10. Weight
Single packing:
250V AC
2000VA (8A / 250V)
8A fast acting
20 x 10
2 x 10
at 1000VA resistive load
max. 6/min at 1000VA resistive load
(in accordance with IEC 60947-5-1)
III (in accordance with IEC 60664-1)
4kV
terminals A1-B1
yes
10m
±1% of maximum scale value
<5% of maximum scale value
<0.5% or ±5ms
-
≤0.01% / °C
-25 to +55°C
-25 to +70°C
-25 to +70°C
15% to 85%
(in accordance with IEC 60721-3-3 class 3K3)
2, if built in 3
(in accordance with IEC 60664-1)
106g
5
6
operations
operations
E3ZM20