2469-53-54-0-AFA-1 YOKOGAWA, 2469-53-54-0-AFA-1 Datasheet - Page 11

TRANSDUCER, WATT, 60HZ, 0-1mA DC

2469-53-54-0-AFA-1

Manufacturer Part Number
2469-53-54-0-AFA-1
Description
TRANSDUCER, WATT, 60HZ, 0-1mA DC
Manufacturer
YOKOGAWA
Datasheet

Specifications of 2469-53-54-0-AFA-1

Transducer Function
Watt 3P3W (2 Element)
Transducer Input Current Ac
1A
Transducer Output Type
0-1mADC
Frequency
60Hz
Supply Voltage
120VAC
Lead Free Status / RoHS Status
na
1) GENERAL
2) SPECIFICATIONS
3) STANDARD MODELS (±90° PA)
NOTE: See order format on next page for additional ratings, frequency calibrations, power-up and output options.
Model #
Current input / range
Current input over range capability
Current input burden
Voltage inputs and range:
Voltage input burden per element
Sustained Voltage input overange
Rated outputs
Accuracy
Output calibration
External calibration adjustment
Response time
Output ripple
Isolation
Surge Withstand Capability
Insulation resistance
Operating temperature
Operating humidity
Temperature effect
External magnetic field
Influence of frequency
Influence of input Voltage
Influence of input Current
Low current detection
Weight
Shock
Vibration
UL Recognition
PA- Single phase / ±1mA output
PA- Single phase / 12±8mA output
PA- 3P3W balanced / ±1mA output
PA- 3P3W balanced / 12±8mA output
PA- 3P4W balanced / ±1mA output
PA- 3P4W balanced / 12±8mA output
The 2469 and 2489 Phase Angle transducers have an analog output corresponding to the phase angle of
the input current relative to the input voltage signal. The analog output will indicate leading or lagging
Phase Angle by its direction from center which would be either 0 mA or 12mA based on output selection.
120V, 5A, 60 Hz, ±90°, input powered
Auxiliary power supply options <5.0 VA burden.
Input powered range
Auxiliary powered range
J U X T A
P H A S E
4-12-20 mADC into a 750Ω max. load; 15VDC output compliance
150% of rated input without damage (Auxiliary powered only)
0.3% of FS peak-to-peak max.
100-135VAC
IEEE472/ANSI C37.90.1 - 1989, JIS C1111 (5KV 1.2 x 50 microseconds)
±1mADC into a 10kΩ max. load; 10VDC output compliance
< 0.5VA
A N G L E
120V
±500 PPM / °C of span
Span: ± 2% minimum
<0.2%, 45 - 65 Hz, fundamental through 9th harmonic
Zero: ± 1% minimum
2469 (±2° Accuracy)
0-120% rated input
60°- 0°- 60° Phase Angle or 90°- 0°- 90° Phase Angle
246976-540-AFB-0-P
246976-540-AHF-0-P
246977-540-AFB-0-P
246977-540-AHF-0-P
246978-540-AFB-0-P
246978-540-AHF-0-P
> 10 megohm / 500VDC input/output/power/case
±2° Phase Angle
16
0 - 90% relative humidity (non-condensing)
2500 VAC input to output, power and case
2000 VAC aux. power to output and case
<1° after 16.7 Hz, 4 mmp-p 1 hour, 3 Axis
<1° after 50G, 3 Axis and 6 repetitions
<1.0°
2469
< 400 milliseconds (0-99% of output)
<0.5°
N/A
1000% of rated input for 5 seconds
200% of rated input continuous
T R A N S D U C E R S
200-264VAC
0-1 Amp AC or 0-5 Amp AC
10 to 200% of rated input
< 1.0VA
500 VAC output to case
< 0.2VA per element
240V
< 0.2% at 400 AT/m
1000g (2.2 lbs.)
-20°C to +60°C
File # E60579
<0.5° ±20% rated Voltage input (aux.pwr.)
<1° for 20-200% rated input current
<0.5° in range af aux. pwr. (int. pwr. model)
0.5% of FS peak-to-peak max.
85-135VAC
< 0.5VA
Span: ± 10% minimum
0-120% of rated input
120V
Zero: ± 5% minimum
±80 PPM / °C of span
2489 (±1° Accuracy)
248976-540-AFB-0-P
248976-540-AHF-0-P
248977-540-AFB-0-P
248977-540-AHF-0-P
248978-540-AFB-0-P
248978-540-AHF-0-P
4% of rated input
±1° Phase Angle
2489
170-264VAC
< 1.0VA
240V