H3BA-N 110 VAC Omron, H3BA-N 110 VAC Datasheet - Page 14

Multi Timer 11 Pin

H3BA-N 110 VAC

Manufacturer Part Number
H3BA-N 110 VAC
Description
Multi Timer 11 Pin
Manufacturer
Omron
Datasheet

Specifications of H3BA-N 110 VAC

Time Range
0.05s To 300hr
Power Consumption
1.6W
Reset Time
0.1s
Rohs Compliant
Yes
Lead Free Status / RoHS Status
Lead free / RoHS Compliant
H3BH-N8
Specifications
Note: If the above minimum power ON time is not secured, the H3BH-N8 may not operate. Be sure to secure the above minimum power ON
14
Operating/Reset method
Pin type
Input type
Output type
Mounting method
Approved standards
Time unit
Setting
Min. power ON time
Limit-time repeat cycle
Rated supply voltage
Operating voltage range
Power consumption
Control outputs
Accuracy of operating time
Setting error
Influence of voltage
Influence of temperature
Insulation resistance
Dielectric strength
Impulse withstand voltage
Noise immunity
Static immunity
Vibration resistance
Shock resistance
Ambient temperature
Ambient humidity
Life expectancy
Case color
Enclosure ratings
Weight
General
Time Ranges
Ratings
Characteristics
time.
Item
Instantaneous operation/Time-limit reset
8-pin
---
Relay output (DPDT)
DIN track mounting, surface mounting, and flush mounting
UL508, CSA C22.2 No.14
0.6
1.2
6
12
0.05 to 0.6
0.1 to 1.2
0.5 to 6
1 to 12
0.1 sec min.
3 s min.
110 VAC (50/60 Hz), 220 VAC (50/60 Hz)
85% to 110% of rated supply voltage
110 VAC:
220 VAC:
Contact output: 5 A at 250 VAC, resistive load (cosφ = 1)
±0.3% FS max. (±0.3% FS ±10 ms in ranges of 0.6 and 1.2 s)
±5% FS ±0.05 s max.
±0.5% FS max. (±0.5% FS ±10 ms in ranges of 0.6 and 1.2 s)
±2% FS max. (±2% FS ±10 ms in ranges of 0.6 and 1.2 s)
100 MΩ min. (at 500 VDC)
2,000 VAC, 50/60 Hz for 1 min (between current-carrying metal parts and exposed
non-current-carrying metal parts)
2,000 VAC, 50/60 Hz for 1 min (between control output terminals and operating circuit)
1,000 VAC, 50/60 Hz for 1 min (between contacts not located next to each other)
3 kV (between power terminals)
4.5 kV (between current-carrying terminal and exposed non-current-carrying metal parts)
±1.5 kV (between power terminals), square-wave noise by noise simulator
(pulse width: 100 ns/1 µs, 1-ns rise)
Malfunction: 8 kV
Destruction: 15 kV
Destruction:10 to 55 Hz with 0.75-mm single amplitude each in three directions
Malfunction:10 to 55 Hz with 0.5-mm single amplitude each in three directions
Destruction: 1,000 m/s
Malfunction: 100 m/s
Operating:–10°C to 55°C (with no icing)
Storage: –25°C to 65°C (with no icing)
Operating: 35% to 85%
Mechanical:10 million operations min. (under no load at 1,200 operations/h)
Electrical:
Light Gray (Munsell 5Y7/1)
IEC: IP40 (panel surface)
Approx. 120 g
Approx. 0.17 VA (0.15 W)
Approx. 0.24 VA (0.18 W)
100,000 operations min. (5 A at 250 VAC, resistive load at 1,200 operations/h)
S-series
s (sec)
2
(approx. 10G) each in three directions
2
(approx. 100G) each in three directions
H3BH-N8
2 sec min.
M-series
min
H3BH-N8

Related parts for H3BA-N 110 VAC