CPM2C-20EDR Omron, CPM2C-20EDR Datasheet - Page 9

Expansion I/O Modules

CPM2C-20EDR

Manufacturer Part Number
CPM2C-20EDR
Description
Expansion I/O Modules
Manufacturer
Omron
Datasheet

Specifications of CPM2C-20EDR

Output Type
Relay
External Width
33mm
Supply Voltage Max
24VDC
External Depth
65mm
Mounting Type
DIN Rail
External Height
90mm
Approval Bodies
UL, CSA, CE
Rohs Compliant
Yes
Lead Free Status / RoHS Status
Lead free / RoHS Compliant
CPU Characteristics table notes:
Note: 1. The DM area, HR area, AR area, and counter values are backed up. If the backup battery or capacitor is discharged, the con-
J I/O ALLOCATION
Input bits
Output bits
Work bits
Special bits (SR area)
Temporary bits (TR area)
Holding bits (HR area)
Auxiliary bits (AR area)
Link bits (LR area)
Timers/Counters
Data memory
A--100
2. The contents of the program area, read-only DM area (DM 6144 to DM 6599), and PC setup (DM 6600 to DM 6655) are stored
tents of these ares will be lost and the data values will revert to the defaults.
in flash memory. The contents of these areas will be read from flash memory the next time the power is turned ON, even if the
backup battery or capacitor is discharged.
When data has been changed in any of these areas, write the new values to flash memory by switching the CMP2C to MON-
ITOR or RUN mode, or by turning the power OFF and then ON again.
Micro Programmable Controller
IR 00000 to IR 00915 (Words not used for input bits can be used for work bits.)
IR 01000 to IR 01915 (Words not used for output bits can be used for work bits.)
928 bits: IR 02000 to IR 04915 (Words IR 020 to IR 049) and
IR 20000 to IR 22715 (Words IR 200 to IR 227)
448 bits: SR 22800 to SR 25515
8 bits (TR0 to TR7)
320 bits: HR 0000 to HR 1915 (Words HR 00 to HR 19)
384 bits: AR 0000 to AR 2315 (Words AR 00 to AR 23)
256 bits: LR 0000 to LR 1515 (Words LR 00 to LR 15)
256 timers/counters (TIM/CNT 000 to TIM/CNT 255)
Read/Write: 2,048 words (DM 0000 to DM 2047)*
Read-only: 456 words (DM 6144 to DM 6599)
PC Setup: 56 words (DM 6600 to DM 6655)
*The Error Log is contained in DM 2000 to DM 2021.
1-ms timers: TMHH(—)
10-ms timers: TIMH(15)
100-ms timers: TIM
1-s/10-s timers: TIML(—)
Decrementing counters: CNT
Reversible counters: CNTR(12)
CPM2C