E5AN-HSS2HBMD-500 Omron, E5AN-HSS2HBMD-500 Datasheet - Page 24

no-image

E5AN-HSS2HBMD-500

Manufacturer Part Number
E5AN-HSS2HBMD-500
Description
CONTROLLER TEMP 24VAC/DC
Manufacturer
Omron
Datasheet

Specifications of E5AN-HSS2HBMD-500

Thermocouple Type
B, E, J, K, L, N, R, S, T, W, PLII
Operating Temperature Max
55°C
Operating Temperature Min
-10°C
Output Voltage Max
250VAC
Output Voltage Min
75VAC
Svhc
No SVHC (15-Dec-2010)
Lead Free Status / RoHS Status
Lead free / RoHS Compliant
Mounting
Mounting to a Panel
For waterproof mounting, waterproof packing must be installed on the
Controller. Waterproofing is not possible when group mounting
several Controllers. Waterproof packing is not necessary when there
is no need for the waterproofing function.
E5EN/E5AN
1. Insert the E5AN/E5EN into the square mounting hole in the panel
2. Use a ratchet to alternately tighten the screws on the top and
Mounting the Terminal Cover
E5AN/E5EN
Slightly bend the E53-COV16 Terminal Cover to attach it to the
terminal block as shown in the following diagram. The Terminal Cover
cannot be attached in the opposite direction.
24
(thickness: 1 to 8 mm). Attach the Mounting Brackets provided with
the product to the mounting grooves on the top and bottom
surfaces of the rear case.
bottom Mounting Brackets little by little to maintain balance, until
the ratchet turns freely.
Advanced Digital Temperature Controller
E53-COV16
Terminal Cover
(Accessory)
E53-COV16
Terminal Cover
(Accessory)
Mounting Bracket
(Accessory)
Mounting Bracket
(Accessory)
Waterproof
packing
(Accessory)
Waterproof
packing
(Accessory)
E53-COV16
Terminal Cover
(Accessory)
Slightly bend the
E53-COV16
Terminal Cover in
the direction shown
by the arrows to
attach it to the
terminal block.
Panel
E5AN
E5EN
Panel
E5@N/E5@N-H
Removing the Temperature Controller from the
Case
The Temperature Controller can be removed from the case to perform
maintenance without removing the terminal leads. This is possible
for only the E5CN, E5AN, and E5EN, and not for the E5CN-U.
Check the specifications of the case and Temperature Controller
before removing the Temperature Controller from the case.
E5AN/E5EN
1. Insert a flat-blade screwdriver into the two tool insertion holes (one
2. Insert the flat-blade screwdriver in the gap between the front panel
3. When inserting the body of the Temperature Controller into the
Precautions when Wiring
• Separate input leads and power lines in order to prevent external
• Use wires with a gage of AWG24 (cross-sectional area:
• Use crimp terminals when wiring the terminals.
• Tighten the terminal screws to a torque of 0.74 to 0.90 N·m,
• Use the following types of crimp terminals for M3.5 screws.
• Do not remove the terminal block. Doing so will result in
on the top and one on the bottom) to release the hooks.
and rear case (two on the top and two on the bottom), and use it to
pry and pull out the front panel slightly. Then, pull out on the front
panel gripping both sides. Be sure not to impose excessive force
on the panel.
case, make sure the PCBs are parallel to each other, make sure
that the sealing rubber is in place, and press the E5AN/E5EN
toward the rear case until it snaps into position. While pressing the
E5AN/E5EN into place, press down on the hooks on the top and
bottom surfaces of the rear case so that the hooks securely lock in
place. Make sure that electronic components do not come into
contact with the case.
noise.
0.205 mm
pair cable (stripping length: 5 to 6 mm).
however the terminal screws on the E5CN-U must be tightened to
a torque of 0.5 N·m.
malfunction or failure.
2
) to AWG14 (cross-sectional area: 2.081 mm
E5AN
Tool insertion
hole
(1)
(1)
(2)
(3)
7.2 mm max.
7.2 mm max.
E5EN
Tool insertion
hole
2
) twisted-
(1)
(1)
(2)
(3)