SNAP-PAC-R1 OPTO 22, SNAP-PAC-R1 Datasheet
SNAP-PAC-R1
Specifications of SNAP-PAC-R1
Related parts for SNAP-PAC-R1
SNAP-PAC-R1 Summary of contents
Page 1
... High-speed digital functions are not included. The -FM model is Factory Mutual approved.The -W model adds wireless LAN capability (see page 2 for more information). Built-in functions and comparisons of the SNAP-PAC-R1 and SNAP-PAC-R2 are shown in the table on Part Numbers Part Description Analog/digital/serial rack-mounted con- ...
Page 2
... I/O Mounting Racks SNAP PAC R-series controllers must be connected to the appropriate rack to avoid damage to the controller. Both the SNAP-PAC-R1 and R2 are designed to work with SNAP PAC mounting racks, which are available with positions for Opto 22 SNAP I/O modules. Part numbers are SNAP-PAC-RCK4, SNAP-PAC-RCK8, SNAP-PAC-RCK12, and SNAP-PAC-RCK16 ...
Page 3
... SNAP PAC controllers and brains, reading or changing basic controller configuration, and configuring and testing I/O. Software Availability PAC Project Basic is included with SNAP PAC controllers and is a free download from the Opto 22 website. PAC Project Professional is available for purchase on our website. To get it immediately, you can buy and download the software from the Opto 22 website at www.opto22.com ...
Page 4
... GHz, 5.745–5.825 GHz 2.412–2.472 GHz, 2.484 GHz 15 dBm maximum Reverse polarity SMA (RP-SMA or RSMA) Supported within an SSID (Service Set Identifier) only SNAP PAC I/O units: SNAP PAC R-series and EB-series I/O units 5.0 5.2 VDC @ 1.5 A – Torque: 8 in-lb (0.9 N-m) 0 ° ...
Page 5
... Requires a Wired+Wireless model (SNAP-PAC-R1-W or SNAP-PAC-R2-W). 4 SNAP-PAC-R1s with serial numbers lower than 600,000 are limited to eight 4-channel digital modules per rack; remaining eight can be analog, serial, and high-density digital modules. System Architecture For the network shown in this diagram, either PAC Project Professional or PAC Project Basic can be used. ...
Page 6
... PC running Display Professional OptoOPCServer and OptoDataLink Ethernet switch, network #1 PAC R-series controller segments enterprise traffic from the control network. If you use a Wired+Wireless PAC (SNAP-PAC-R1-W or SNAP-PAC-R2-W), one of these networks can be a wireless LAN. See the following page for an example. Field devices location #2 ...
Page 7
... SNAP PAC R-Series Controllers System Architecture (continued) The network shown in this diagram requires a Wired+Wireless R-series controller (SNAP-PAC-R1-W or SNAP-PAC-R2-W). SNAP PAC R-series Controller Segmenting Wired and Wireless Networks Control Network SNAP-PAC-R1-W Field devices location #1 SNAP-PAC-R1-W wired+wireless controller communicates with host computers through a wired network interface, controls I/O directly on its own rack, and controls one or more remote I/O units on an isolated wireless network ...
Page 8
... SNAP PAC R-series controllers and the SNAP PAC S-series controllers both have two network interfaces, and each PC in this system has two network interface cards. Using a Wired+Wireless PAC (SNAP-PAC-R1-W or SNAP-PAC-R2-W) makes it possible for one of these networks wireless LAN. Ethernet switch, ...
Page 9
... SNAP PAC R-Series Controllers SNAP PAC R-Series Comparison Chart The following table compares SNAP PAC R-series controllers with firmware version 8.5. FEATURE Factory Mutual approval Input latching On/off status Watchdog timer High-speed counting ( kHz) 2 Quadrature counting Digital I/O On-pulse and off-pulse measurement ...
Page 10
... Module types and maximum numbers allowed per I/O unit (with largest rack) 1 4-channel digital modules only; not available on high-density digital modules 2 Requires a SNAP quadrature input module (SNAP-IDC5Q) 3 Requires PAC Control Professional 8.2 or newer, or PAC Control Basic 9.0 or newer 4 Requires a SNAP analog TPO module (SNAP-AOD-29) Opto 22 • ...
Page 11
... Minimum requirements for wiring an RS-232 serial cable to connect to a PC. If you want to connect the controller to a modem, see form #1595, the SNAP PAC R-Series Controllers User’ s Guide, for all eight pin connections. Opto 22 • 43044 Business Park Drive • Temecula, CA 92590-3614 • www.opto22.com ...
Page 12
... Connectors and Indicators (continued) The following information applies to Wired+Wireless models (SNAP-PAC-R1-W and SNAP-PAC-R2-W). Ethernet LEDs Controller reset button LEDs* Indicator ACT LNK STAT 232 WLAN * The WLAN LED replaces the PPP LED on -W models. These models can still communicate using PPP even though they do not have the indicator. ...
Page 13
... SNAP PAC R-Series Controllers Dimensions This diagram applies to all R-series PACs except -W models. See the following page for dimensions on Wired+Wireless R-series PACs. SALES 800-321-6786 • 951-695-3000 • FAX 951-695-3095 • sales@opto22.com • SUPPORT 800-835-6786 • 951-695-3080 • FAX 951-695-3017 • support@opto22.com © ...
Page 14
... Dimensions This diagram applies to Wired+Wireless R-series PACs (SNAP-PAC-R1-W and SNAP-PAC-R2-W). Opto 22 • 43044 Business Park Drive • Temecula, CA 92590-3614 • www.opto22.com PAGE SALES 800-321-6786 • 951-695-3000 • FAX 951-695-3095 • sales@opto22.com • SUPPORT 800-835-6786 • 951-695-3080 • FAX 951-695-3017 • support@opto22.com 14 © ...
Page 15
... TPO, and pulse generation and measurement. SNAP I/O I/O provides the local connection to sensors and equipment. Opto 22 SNAP I/O offers points of reliable I/O per module, depending on the type of module and your needs. Analog, digital, serial, and special-purpose modules are all mixed on the same mounting rack and controlled by the same processor (SNAP PAC brain or rack-mounted controller) ...