61F-GPN2 240AC Omron, 61F-GPN2 240AC Datasheet - Page 3

LEVEL CONTROLLER, MINI, 240V

61F-GPN2 240AC

Manufacturer Part Number
61F-GPN2 240AC
Description
LEVEL CONTROLLER, MINI, 240V
Manufacturer
Omron
Datasheet

Specifications of 61F-GPN2 240AC

Supply Voltage
240V
Response Time
80ms
Power Consumption
3.2W
Svhc
No SVHC (15-Dec-2010)
Ac Coil Power
3.2VA
Approval Bodies
CE, CSA, SEV, UL Recognised
Contact Current Max
5A
Connections
Automatic Water Supply and Drainage Control
1. Water supply
• Connect electromagnetic switch coil terminal A to Tb.
• The pump stops when the water level reaches E1 and starts when
Operation
The conductive type level controller consists of a plug-in controller
connected to a set of stainless steel probes. These are cut to length
and inserted vertically into the liquid. A low voltage is applied
between these probes and the earth probe (or tank, if it is electrically
conductive). The water provides a current between the earth probe
and the high-level probe. The output relay in the controller is ener-
gized when the water level reaches the high-level probe and de-ener-
gized when the water level falls below it.
Dimensions
Note: Note:All units are in millimeters unless otherwise indicated.
the water level drops below E2.
49.4
38
38
Electromagnetic
switch
220 or
240 VAC
MCCB
70
70
84
80
Power source
Conductive Level Controller
R S T
2. Drainage
• Connect the electromagnetic switch coil terminal A to Ta.
• The pump starts when the water level reaches E1 and stops when
Note: 1. The diagram shows the connections for water supply. When
For two-point control a low-level probe is used as well. In this case
the relay does not de-energize until the water level falls below the
low-level probe. Using the low-level probe allows a wide differential
between switching a pump on and off, and can avoid excessive pump
operation during tank emptying or filling. If this differential is not
required, the low-level probe need not be connected.
the water level drops below E2.
M
2. The earth terminal must be grounded.
A
draining, change the connection Tb to Ta.
P
Reservoir
3
2
Tb
Ta
4
1
E3
Tc
61F-GP-N2
S2
E2
8
5
Stop
Start
61F-
GP-N2
PF083A
E1
S1
6
7
91
E1
E2
E3
Earth
Tank
3