ZA120Y Wiremold, ZA120Y Datasheet - Page 9

Suppressors, Outlet

ZA120Y

Manufacturer Part Number
ZA120Y
Description
Suppressors, Outlet
Manufacturer
Wiremold
Series
ZoneMasterr
Datasheets

Specifications of ZA120Y

Suppressor Type
Outlet Strip
Voltage Rating
120VAC
Operating Voltage Range
120VAC To 208VAC
Peak Surge Current
90kA
Connector Type
Terminal Lugs, 4 Wire (#2 AWG Max.)
Data Line Protection
N
Product
Power Outlet Strips
Breakdown Voltage Vbr
330V
Supply Voltage Min
120VAC
Rohs Compliant
No
Applications
Distribution Boards And Small Service Entrance Locations
Lead Free Status / RoHS Status
Contains lead / RoHS non-compliant
Lead Free Status / RoHS Status
Contains lead / RoHS non-compliant
ZoneMaster 180
engineered to withstand the most
severe transient environment at large
service entrance or distribution panels,
and provide decades of uninterrupted
surge protection. Dual protection
circuits provide redundancy ensuring
the site is always protected. The
ZoneMaster 180 Series provides the
lowest suppression voltages available,
90kA surge capacity per mode, as
well as, full protection in all modes
(L-N, L-G, L-L, and N-G).
Mechanical Specifications:
Enclosure:
Dimensions:
Weight:
Operating Environment: -40°C to 85°C, 95% relative humidity (non-condensing)
Construction:
Terminal Lugs:
Mounting:
Module Replacement:
Module Dimensions:
* Testing per ANSI/IEEE C62.45
The ZoneMaster 180 Series is
Remote monitoring unit.
120/240V Single Ø 3 Wire 90kA
120/208V 3Ø 4 Wire WYE 90kA
277/480V 3Ø 4 Wire WYE 90kA
SERVICE VOLTAGE
180 SERIES
Durable, lightweight, corrosion resistant high impact plastic. Ultraviolet stabilized UL94-5V rated.
NEMA 1, 2, 3, 3S, 4, 4X 12, and 13. Transparent cover for maximum visibility and safety.
12" x 12" x 6" (31cm x 31cm x 15.5cm).
Approx. 12 lbs. (5.5 kg)
Low impedance assembly. Modules are bolted (1/4" bolts) to a large surge return plate to minimize
transient impedance and suppression voltage.
#2 AWG max wire size
4" x 0.31" diameter holes 12 3/4" x 10" [30.5cm x 25.4cm]. Enclosure can be easily drilled for
conduit/cable access.
Remove two 1/4" nuts, unplug remote indication connector and remove module. Estimated
replacement time 2 minutes.
1 1/4" x 5 5/16" x 2 1/2" [3.2cm x 13.5cm x 6.4cm]
See page 15 for complete specifications on options.
SUPPRESSION VOLTAGE
400V
400V
800V
L-N
ZoneMaster 180 Options
LEVELS (UL1449)
Electrical Specifications
400V
400V
800V
L-G
9
EMI/RFI noise filter. Noise attenuation -75dB
maximum 100 kHz to 100 MHz.
CAT B3:3KA
ANSI/IEEE C62.41-1992*
395V
395V
875V
(1.2/50µs – 8/20µs)
CAT C3:10KA
1030V
533V
533V
MAXIMUM SURGE
PER PHASE
CURRENT
180,000A
180,000A
180,000A