HDL36040 SQUARE D, HDL36040 Datasheet - Page 32

CIRCUIT BREAKER, THERMAL MAG, 3P, 40A

HDL36040

Manufacturer Part Number
HDL36040
Description
CIRCUIT BREAKER, THERMAL MAG, 3P, 40A
Manufacturer
SQUARE D
Series
PowerPactr
Datasheet

Specifications of HDL36040

Actuator Style
Toggle
No. Of Poles
3
Current Rating
40A
Voltage Rating Vdc
250V
Voltage Rating Vac
600V
Mounting Type
DIN Rail
Terminals
Lug
Lead Free Status / RoHS Status
Lead free / RoHS Compliant
32
PowerPact
Section 2—Mounting and Connections
Drawout Mounting
Plug-In Mounting
06/2010
®
H- and J-Frame Circuit Breakers
Plug-In and Drawout Circuit Breakers
H- and J-frame circuit breakers are available in a plug-in and drawout construction.
Plug-In Circuit Breaker Mounting
The plug-in base is mounted through a front panel. The plug-in configuration makes it possible to:
When the circuit breaker is in the connected position, the primary voltage is fed through the circuit
breaker by means of multiple finger disconnects. Control voltage of internal accessories is provided
through secondary disconnects.
Parts of a Plug-In Configuration
Figure 8:
Table 40:
Description
Kit for H- and J-Frame Circuit Breakers (Stationary and Moving Part)
Consisting of:
Extract and/or rapidly replace the circuit breaker without having to touch connections
Allow for addition of future circuits at a later date
Disconnects: Provides both primary and
secondary disconnect to the circuit
breaker.
Safety Trip Interlock: The safety trip
causes automatic tripping if the circuit
breaker is ON before engaging or
withdrawing it; the safety trip does not
prevent the circuit breaker operation, even
when the circuit breaker is disconnected.
Plug-in Base: The plug-in base provides
mounting through a front panel or mounting
on rails.
Plug-In Base (Mounting Options)
Plug-In Mounting
Stationary Part
Moving Part
Mounting Through
a Front Panel
Plug-In Base
Short Terminal Covers
Safety Trip Interlock
Power Connections
Suffix
N
HJ00
3
6
9
2
5
8
1
4
7
3
6
9
2
5
8
4
7
1
Catalog No.
29293
29278
29321
29270
29268
Primary
Disconnects
Secondary
Disconnects
© 2004–2010 Schneider Electric
(3)
Mounting on Rails
Safety Trip Interlock
Mounted on Back of
Circuit Breaker
All Rights Reserved

Related parts for HDL36040