MY2-02-DC24 Omron, MY2-02-DC24 Datasheet - Page 3

RELAY

MY2-02-DC24

Manufacturer Part Number
MY2-02-DC24
Description
RELAY
Manufacturer
Omron
Series
MYr
Datasheets

Specifications of MY2-02-DC24

Relay Type
General Purpose
Contact Form
DPDT (2 Form C)
Contact Rating (current)
5A
Switching Voltage
250VAC, 125VDC - Max
Coil Type
Standard
Coil Current
36.9mA
Coil Voltage
24VDC
Turn On Voltage (max)
19.2 VDC
Turn Off Voltage (min)
2.4 VDC
Mounting Type
Through Hole
Termination Style
PC Pin
Circuit
DPDT (2 Form C)
Contact Rating @ Voltage
5A @ 220VAC
Control On Voltage (max)
19.2 VDC
Control Off Voltage (min)
2.4 VDC
Coil Voltage Vdc Nom
24V
Contact Current Max
5A
Contact Voltage Ac Nom
220V
Contact Voltage Dc Nom
24V
Coil Resistance
636ohm
Contact Configuration
DPDT
Lead Free Status / RoHS Status
Lead free / RoHS Compliant
Other names
MY2-02-DC24
MY202DC24
SW952
SW952
Z2633
■ Contact Ratings
Note: Don’t exceed the carry current of a Socket in use. Please see page 9.
■ Characteristics
Note: The values given above are initial values.
■ Endurance Characteristics
Rated load
Carry current
Max. switching
voltage
Max. switching
current
Max. switching
power
Failure rate
(reference value)
Contact resistance
Operate time
Release time
Max. operating frequency
Insulation resistance
Dielectric strength
Vibration resistance
Shock resistance
Endurance
Ambient temperature
Ambient humidity
Weight
2-pole
4-pole
4-pole (bifurcated)
Item
Pole
5A, 250 VAC
5A, 30 VDC
10 A (see note)
250 VAC
125 VDC
10 A
2,500 VA
300 W
5 VDC, 1 mA
Item
Resistive load
(cos φ = 1)
AC:50,000,000 operations min.
DC:100,000,000 operations min.
20,000,000 operations min.
Mechanical life (at 18,000 operations/hr)
2-pole
2A, 250 VAC
2 A, 30 VDC
1,250 VA
300 W
(cos φ = 0.4, L/R = 7 ms)
Inductive load
100 m Ω max.
20 ms max.
20 ms max.
Mechanical: 18,000 operations/hr
Electrical:
1,000 M Ω min. (at 500 VDC)
2,000 VAC, 50/60 Hz for 1.0 min (1,000 VAC between contacts of same polarity)
Destruction: 10 to 55 to 10 Hz, 0.5 mm single amplitude (1.0 mm double amplitude)
Malfunction: 10 to 55 to 10 Hz, 0.5 mm single amplitude (1.0 mm double amplitude)
Destruction: 1,000 m/s
Malfunction: 200 m/s
See the following table.
Operating: –55 ° C to 70 ° C (with no icing)
Operating: 5% to 85%
Approx. 35 g
1,800 operations/hr (under rated load)
3 A, 250 VAC
3 A, 30 VDC
5 A (see note)
250 VAC
125 VDC
5 A
1,250 VA
150 W
1 VDC, 1 mA
Resistive load
(cos φ = 1)
2
2
General-purpose Relay
0.8 A, 250 VAC
1.5 A, 30 VDC
500 VA
150 W
4-pole
(cos φ = 0.4, L/R = 7 ms)
Inductive load
500,000 operations min.
200,000 operations min.
100,000 operations min.
All Relays
(at 1,800 operations/hr under rated load)
MY New model
3 A, 250 VAC
3 A, 30 VDC
1,250 VA
150 W
1 VDC, 100 µ A
Resistive load
(cos φ = 1)
Electrical life
4-pole (bifurcated)
0.8 A, 250 VAC
1.5 A, 30 VDC
500 VA
150 W
(cos φ = 0.4, L/R = 7 ms)
Inductive load
3

Related parts for MY2-02-DC24