J OVERLOAD PROTECTION
The protective function prevents damage to the load as well as to
the power supply itself due to overload. If the load current rises
above the overload set value (105% to 135% of the rated load
current), the protective function will engage, and the voltage will
be reduced. Reset is automatic, so the power supply will return to
normal operation when the overload condition is corrected.
If the output voltage falls below 70% of the rated value in an
overload condition, the low-voltage sensing circuit will engage
and shut off the output if the low voltage condition continues for
more than 5 s. In this situation, reset is not automatic. To reset
the power supply, turn off the input power for at least 30 s and
then turn it on again.
J INRUSH CURRENT, START UP TIME, HOLD TIME
AC input
voltage
AC input
current
Output
voltage
4
Input ON
Inrush current on input application
Switching Power Supply
Start up time
300 ms max.
S82D
Input OFF
Hold time
20 ms min.
Output shut off after 5 s
Output current (%)
Rated voltage