12SWUDC AMPERITE, 12SWUDC Datasheet - Page 5

no-image

12SWUDC

Manufacturer Part Number
12SWUDC
Description
PCB, Solid State Relay, Control Voltage AC Max. 12 Volt, Control Voltage DC Max. 12 Volt.
Manufacturer
AMPERITE
Datasheet

Specifications of 12SWUDC

Brand/series
SWUDC Series
Contact Form
DPDT-NO⁄NC
Current, Rating
10, 15 A
Function
Timing
Mounting Type
PCB
Number Of Pins
11
Relay Type
Solid State
Standards
UL, CSA
Temperature, Operating, Maximum
70 °C
Temperature, Operating, Minimum
-45 °C
Termination
Plug-In
Timer Type
Multi-Function
Timing Range
72 to 360 sec.
Voltage, Control
12 VAC⁄VDC
Voltage, Rating
120, 240⁄30 VAC⁄VDC
Time Delay Range
A: .1 sec. to 15.5 secs.
B: 10 secs. to 25 mins.
C: 10 mins. to 25 hrs.
D: 30 mins. to 77.5 hrs. Off
*Choose the range which most narrowly incorporates the time delay you desire. e.g. for
180 secs. Choose range B and set S1 to Off and S2 to On.
2) Calculating The Multiplier For The Desired Time Delay
Dip Switch positions S3 - S7 are used to set the multiplier which will customize your
time delay range. The values for these settings are as follows:
Switch Position Multiplier Value
S3
S4
S5
S6
S7
The Formula
Once you have chosen the appropriate basic timing range, perform the following
calculations - (to clarify the steps use the desired time delay of 180 secs. as an example):
A) For 180 seconds select range B (10 secs. to 25 mins.).
B) Divide the desired time delay (180 secs.) by the minimum time of the selected range.
(minimum time in range B is 10 secs.) 180/10 = 18. Always convert to the same time
units (min., sec., hrs.) when dividing.
C) The multiplier is equal to 1/2 of this quotient - 180/10 = 18. 18/2 = 9, therefore the
multiplier for 180 seconds is 9 and the user must set switches S3- S7 as follows:
Total = 31
16
8
4
2
1
Solving your relay requirements since 1922
Switch Position
S1
On
Off
On
S2
On
On
Off
On

Related parts for 12SWUDC