MY3N-DC100/110 Omron, MY3N-DC100/110 Datasheet - Page 2

RELAY

MY3N-DC100/110

Manufacturer Part Number
MY3N-DC100/110
Description
RELAY
Manufacturer
Omron
Series
MYr
Datasheets

Specifications of MY3N-DC100/110

Relay Type
General Purpose
Contact Form
3PDT (3 Form C)
Contact Rating (current)
5A
Switching Voltage
250VAC, 125VDC - Max
Coil Type
Standard
Coil Current
9.1mA
Coil Voltage
110VDC
Turn On Voltage (max)
88 VDC
Turn Off Voltage (min)
11 VDC
Mounting Type
Socket
Termination Style
Socketable
Circuit
3PDT (3 Form C)
Contact Rating @ Voltage
5A @ 220VAC
Control On Voltage (max)
88 VDC
Control Off Voltage (min)
11 VDC
Lead Free Status / RoHS Status
Lead free / RoHS Compliant
Lead Free Status / RoHS Status
Lead free / RoHS Compliant
Other names
MY3NDC100110
Specifications
■ Coil Ratings
Note: 1. The rated current and coil resistance are measured at a coil temperature of 23°C with tolerances of +15%/–20% for rated currents and
■ Contact Ratings
Note: Do not exceed the carry current of a Socket in use.
260
Rated voltage
AC
DC
Item
Rated load
Carry current
Max. switching
voltage
Max. switching
current
Max. switching
capacity
Min.
permissible
load*
* Reference value.
2. Performance characteristic data are measured at a coil temperature of 23°C.
3. AC coil resistance and impedance are provided as reference values (at 60 Hz).
4. Power consumption drop was measured for the above data. When driving transistors, check leakage current and connect a bleeder re-
5. Rated voltage denoted by “*” will be manufactured upon request. Ask your OMRON representative.
6 V*
12 V
24 V
48/50 V*
110/120 V
220/240 V
6 V*
12 V
24 V
48 V*
100/110 V
±15% for DC coil resistance.
sistor if required.
General-purpose Relay
2-pole
Resistive load
(cosφ = 1)
5 A, 250 VAC
5 A, 30 VDC
10 A (see note)
250 VAC
125 VDC
10 A
2,500 VA
300 W
5 VDC, 1 mA
Rated current
50 Hz
214.1 mA
106.5 mA
53.8 mA
24.7/
25.7 mA
9.9/10.8 mA 8.4/9.2 mA
4.8/5.3 mA 4.2/4.6 mA
151 mA
75 mA
37.7 mA
18.8 mA
9.0/9.9 mA
60 Hz
183 mA
91 mA
46 mA
21.1/
22.0 mA
Inductive load
(cosφ = 0.4,
L/R = 7 ms)
2 A, 250 VAC
2 A, 30 VDC
1,250 VA
300 W
MY
Coil
resistance
12.2 Ω
46 Ω
180 Ω
788 Ω
4,430 Ω
18,790 Ω
39.8 Ω
160 Ω
636 Ω
2,560 Ω
11,100 Ω
4-pole
Resistive load
(cosφ = 1)
3 A, 250 VAC
3 A, 30 VDC
5 A (see note)
250 VAC
125 VDC
5 A
1,250 VA
150 W
1 VDC, 1 mA
Inductance
(reference value)
Arm. OFF
0.04 H
0.17 H
0.69 H
3.22 H
19.20 H
83.50 H
0.17 H
0.73 H
3.20 H
10.60 H
45.60 H
Inductive load
(cosφ = 0.4,
L/R = 7 ms)
0.8 A, 250 VAC
1.5 A, 30 VDC
500 VA
150 W
Arm. ON
0.08 H
0.33 H
1.30 H
5.66 H
32.1 H
136.4 H
0.33 H
1.37 H
5.72 H
21.0 H
86.2 H
Must
operate
% of rated voltage
80% max. 30% min. 110%
4-pole (bifurcated)
Resistive load
(cosφ = 1)
3 A, 250 VAC
3 A, 30 VDC
1,250 VA
150 W
1 VDC, 100 μA
Must
release
10% min.
Max.
voltage
Inductive load
(cosφ = 0.4,
L/R = 7 ms)
0.8 A, 250 VAC
1.5 A, 30 VDC
500 VA
150 W
Power
consumption
(approx.)
1.0 to 1.2 VA
(60 Hz)
0.9 to 1.1 VA
(60 Hz)
0.9 W

Related parts for MY3N-DC100/110