H5CX-L8D-N DC12-24/AC24 Omron, H5CX-L8D-N DC12-24/AC24 Datasheet - Page 28

no-image

H5CX-L8D-N DC12-24/AC24

Manufacturer Part Number
H5CX-L8D-N DC12-24/AC24
Description
8-PIN, RLY OUT, Limit, Instant DC12-24/AC24
Manufacturer
Omron
Series
H5CXr
Datasheet

Specifications of H5CX-L8D-N DC12-24/AC24

Relay Type
Integrated
Function
Programmable (Multi-Function)
Circuit
SPDT (1 Form C)
Delay Time
0.001 Sec ~ 9999 Hrs
Output Type
Mechanical Relay
Contact Rating @ Voltage
5A @ 250VAC
Voltage - Supply
12 ~ 24VDC, 24VAC
Mounting Type
Socket
Termination Style
8 Pin Socketable
Timing Adjustment Method
Up/Down Digit Keys
Timing Initiate Method
Input Voltage, Trigger Signal
Lead Free Status / RoHS Status
Lead free / RoHS Compliant
Other names
H5CXL8DNDC1224AC24
Z3000
Explanation of Functions
OFF Time Range (oftr) (Setting possible using DIP
switch.)
Set the time range for the OFF time in the range 0.000 s to 9,999 h.
Only settings of type --.-- s (99.99 s), ---.- s (999.9 s), ---- s (9,999 s),
and -- min -- s (99 min 59 s), however, can be made with the DIP
switch. Use the operation keys if another type of setting is required.
ON Time Range (ontr) (Setting possible using DIP
switch.)
Set the time range for the ON time in the range 0.001 s to 9,999 h.
Only settings of type --.-- s (99.99 s), ---.- s (999.9 s), ---- s (9,999 s),
and -- min -- s (99 min 59 s), however, can be made with the DIP
switch. Use the operation keys if another type of setting is required.
Timer Mode (timm) (Setting possible using DIP switch.)
Set either UP (incremental) or DOWN (decremental) timer mode. In
UP mode, the elapsed time is displayed, and in DOWN mode, the
remaining time is displayed.
ON/OFF Start Mode (totm) (Setting possible using DIP
switch.)
Set the output mode. Set either flicker OFF start or flicker ON start.
(For details on output mode operation, refer to Timing Charts on
page 30.)
Key Protect Level (kypt)
Set the key protect level.
When the key-protect switch is set to ON, it is possible to prevent setting errors by prohibiting the use of certain operation keys by specifying the
key protect level (KP-1 to KP-5). The key protect indicator is lit while the key-protect switch is set to ON.
Note: Changing mode to timer/twin timer selection mode (
KP-1
(default setting)
KP-2
KP-3
KP-4
KP-5
Note: Factory-set to OFF
(See note)
Level
OFF
ON
Key protect indicator
Meaning
No
No
No
No
No
Changing mode
(See note.)
MODE
+
1
Yes
Yes
Yes
Yes
No
1 s min.) or function setting mode (
Switching display
during operation
Input Signal Width (iflt) (Setting possible using DIP
switch.)
Set the minimum signal input width (20 ms or 1 ms) for signal, reset,
and gate inputs. The same setting is used for all external inputs (sig-
nal, reset, and gate inputs). If contacts are used for the input signal,
set the input signal width to 20 ms. Processing to eliminate chatter-
ing is performed for this setting.
NPN/PNP Input Mode (imod)
Select either NPN input (no-voltage input) or PNP input (voltage
input) as the input format. The same setting is used for all external
inputs. For details on input connections, refer to Input Connections
on page 9.
Display Color (colr)
Set the color used for the present value.
red
grn
r-g
g-r
Red (fixed)
Green (fixed)
Red
Green
Details
Output OFF
Yes
No
Yes
No
No
Reset key
MODE
3 s min.).
Green
Red
Yes
Yes
No
No
No
H5CX-A/-L
Output ON
Up/down key
28